Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ALABAMA POWER COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ALABAMA POWER COMPANY in 4250 PORTER ROAD, QUINTON, AL 35130 (NAICS 221119). OSHA activity number 340463520.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Alabama Power Company — free Get an email when a new federal OSHA severe-injury report for Alabama Power Company is published. One employer, no account, unsubscribe in one click.
Site address
4250 PORTER ROAD
City
QUINTON
State
AL
ZIP
35130
Mailing
4250 PORTER ROAD, QUINTON, AL 35130
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221119
Employees
368
Ownership type
A

3 citations on file for this inspection.

1910.119 F01

Serious Gravity 10 1 instance 2 exposed
Issued
Aug 28, 2015
Abate by
Sep 17, 2015
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.119(f)(1): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process consistent with the process safety information:  (a) On or about 3/13/15 - at Units 3 & 4 Cooling Tower Chlorinator, the written operating procedure MILL-00-06001.10 Rev 0, Operation of Cooling Tower Chlorinator Systems did not provide clear instructions for emptying a cylinder in manual mode and performing a flush.
Recent events (1)
  • — Z (S) $7000

1910.132 A

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 28, 2015
Penalty
Initial $3,750 · Current $3,750
29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered:  (a) On or about 3/10/15 - at Units 3 & 4 Cooling Tower Chlorinator, an employee responding to a chlorine leak did not use gloves (butyl rubber, neoprene, nitrile, or PVC) and PVC rain suit to respond to a minor leak as identified in Miller Laboratory Procedures MILL-00-06--1.14 R1, Chlorine Leak Response.
Recent events (1)
  • — Z (S) $3750

1910.119 L05

Other-than-serious 1 instance 9 exposed
Issued
Aug 28, 2015
Abate by
Sep 17, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.119(l)(5): A change covered by this paragraph resulted in a change in the operating procedures or practices required by paragraph (f) of this section, and such procedures or practices were not updated accordingly:  (a) On or about 03/13/15 - at Units 3 & 4 Cooling Tower Chlorinator, MILL-00-06001.10 Rev. 0, Operation of Cooling Tower Chlorinator Systems was not updated to reflect the change in MOC 14-02 that changed the control panels to allow for automatic cycling of the chlorination equipment in parallel versus one unit at a time.
Recent events (1)
  • — Z (O) $0

View Alabama Power Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340463520.