JOHNSTOWN, NY —
OSHA Inspection: WALMART DC 6096
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of WALMART DC 6096 in 300 ENTERPRISE ROAD, JOHNSTOWN, NY 12095 (NAICS 493120). OSHA activity number 340473461.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WALMART DC 6096
- Site address
- 300 ENTERPRISE ROAD
- City
- JOHNSTOWN
- State
- NY
- ZIP
- 12095
- Mailing
- 300 ENTERPRISE ROAD, JOHNSTOWN, NY 12095
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493120
- Employees
- 700
- Ownership type
- A
Citations
1 citation on file for this inspection.
1910.119 J05
- Issued
- Jul 14, 2015
- Abate by
- Aug 16, 2015
- Penalty
- Initial $5,000 · Current $3,750 Reduced
General-duty citation text
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) before use: (a) Condenser unit platform, north side, at condenser unit(s): On or prior to 3/27/15, HSD (high pressure vapor) and CD (high pressure liquid) ammonia lines and PSV assembly(s) showed evidence of external paint coating failure and corrosion. (b) Roof of energy center: On or prior to 3/27/15, Hot Gas King Valve pipe and valve assembly was showed evidence of external paint coating failure and corrosion. (c) Main roof of refrigerated building: On or prior to 3/27/15, roof-top valve assembly(s), including PSVs, for air curtain AHUs and penthouse AHUs showed evidence of external paint coating failure and corrosion.
Recent events (2)
- — I (O) $3750
- — Z (S) $5000
More inspections in this industry (NAICS 493120)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340473461.