CORDOVA, IL —
OSHA Inspection: EXELON GENERATION COMPANY, LLC
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of EXELON GENERATION COMPANY, LLC in 22710 206TH AVE N, CORDOVA, IL 61242 (NAICS 221113). OSHA activity number 340481332.
Where did this inspection happen?
- Establishment
- EXELON GENERATION COMPANY, LLC
- Site address
- 22710 206TH AVE N
- City
- CORDOVA
- State
- IL
- ZIP
- 61242
- Mailing
- 22710 206TH AVE N, CORDOVA, IL 61242
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221113
- Employees
- 1500
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.269 D06
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.269(d)(6): The established procedures for the application of energy control (the lockout or tagout procedures) shall include the following elements and actions, and these procedures shall be performed in the following sequence: On March 14, 2015 the employer directed its contractor to remove electrical insulators in close proximity to energized parts in Cubicle 9, Bus 12, and was not required to perform the following steps before starting work: (1) know the type and magnitude of the energy, the hazards of the energy to be controlled, and the method or means to control the energy, (2) turn off and shut down the machines or equipment, (3) physically locate and operate energy isolating devices in such a manner as to isolate the machine or equipment from the energy source, (4) affix lockout or tagout devices to each energy isolating device, (5) prior to starting work on machines or equipment that have been locked out or tagged out, verify that isolation and de-energization of the machine or equipment have been accomplished. The employee was required to rely upon the system operator and was exposed to electrocution/high voltage electric shock.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.269 D08 IV
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $7000.00
General-duty citation text
29 CFR 1910.269(d)(8)(iv): Whenever outside servicing personnel are to be engaged in activities covered by paragraph (d) of this section, the on-site employer and the outside employer shall inform each other of their respective lockout or tagout procedures, and each employer shall ensure that his or her personnel understand and comply with restrictions and prohibitions of the energy control procedures being used: On March 14, 2015, the employer failed to ensure that its employees understood and complied with the procedures, restrictions, or prohibitions or the energy control procedures being used.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.269 D08 V B
- Issued
- Abate by
- Penalty
- Initial $7000.00 · Current $7000.00
General-duty citation text
29 CFR 1910.269(d)(8)(v)(B): The system operator did not place and remove tagout devices in place of the authorized employee under paragraphs (d)(4), (d)(6)(iv), and (d)(7)(iv) of this section: On March 14, 2015, the employer directed its contractor to remove three electrical insulators in close proximity to energized parts, located in Cubical 9, Bus 12, but failed to ensure that their system operator de-energized the equipment being maintained before the start of work. The employee was exposed to electrocution/high voltage electric shock.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
More inspections at EXELON GENERATION COMPANY, LLC
LUSBY, MD—2019-12-06 00:00:00
EXELON GENERATION COMPANY, LLC
MARSEILLES, IL—2019-11-12 00:00:00
EXELON GENERATION COMPANY, LLC
MEDWAY, MA—2019-08-14 00:00:00
EXELON GENERATION COMPANY, LLC
LUSBY, MD—2018-03-08 00:00:00
EXELON GENERATION COMPANY, LLC
MORRIS, IL—2018-01-30 00:00:00
EXELON GENERATION COMPANY, LLC
View EXELON GENERATION COMPANY, LLC's full OSHA safety record →
More inspections in this industry (NAICS 221113)
SEABROOK, NH—2026-06-03
NEXTERA ENERGY SEABROOK, LLC
COVERT, MI—2026-05-19
HOLTEC PALISADES, LLC
BYRON, IL—2026-03-12
CONSTELLATION ENERGY GENERATION, LLC
TWO RIVERS, WI—2026-02-19
NEXTERA ENERGY POINT BEACH, LLC
PENDLETON, SC—2026-02-14
77271 - DUKE ENERGY OCONEE NUCLEAR STATION
More inspections in IL
BLOOMINGTON, IL—2026-07-13
UNKNOWN CONTRACTOR
GRANITE CITY, IL—2026-07-13
UNITED STATES STEEL CORPORATION
DECATUR, IL—2026-07-10
TILLAMOOK ILLINOIS, LLC
NEW LENOX, IL—2026-07-10
A.D GENERAL CONSTRUCTION LLC
LOCKPORT, IL—2026-07-09
ROBERTO GOMEZ DBA ROBERTO GOMEZ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340481332.