Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NORTHERN ELECTRIC COOPERATIVE

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of NORTHERN ELECTRIC COOPERATIVE in 182ND STREET & 401ST AVENUE, FRANKFORT, SD 57440 (NAICS 221122). OSHA activity number 340482793.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Northern Electric Cooperative — free Get an email when a new federal OSHA severe-injury report for Northern Electric Cooperative is published. One employer, no account, unsubscribe in one click.
Site address
182ND STREET & 401ST AVENUE
City
FRANKFORT
State
SD
ZIP
57440
Mailing
P.O. BOX 457, BATH, SD 57427
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
Yes
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
37
Ownership type
A

2 citations on file for this inspection.

1910.269 O02 I

Other-than-serious 1 instance 3 exposed
Issued
Jul 30, 2015
Abate by
Aug 18, 2015
Penalty
Initial $4,900 · Current $3,900 Reduced
29 CFR 1910.269(o)(2)(i): The employer did not establish and enforce work practices for the protection of each employee from the hazards of high-voltage or high-power testing at all test areas, temporary and permanent that include, at a minimum, test area safeguarding, grounding, the safe use of measuring and control circuits, and a means providing for periodic safety checks of field test areas:    (a) On or about March 11, 2015 and at times prior to that date, for the employees exposed to electrical shock hazards while operating a VON model XF 16-1280, Serial Number 610262, Arc-Reflection test system to locate an underground electrical fault at the vicinity of 182nd Street & 401st Avenue, Frankfort, South Dakota.
Recent events (3)
  • — F (O) $3900
  • — C (S) $4900
  • — Z (S) $4900

1910.269 O04 III B

Other-than-serious Gravity 10 1 instance 3 exposed
Issued
Jul 30, 2015
Abate by
Aug 11, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.269(o)(4)(iii)(B): During high-power testing, the employer did not protect employees from hazardous step and touch potentials that may develop during the test:      (a) On or about March 11, 2015, for the employee that was shocked while locating an underground electrical fault utilizing a VON model XF 16-1280, Serial Number 610262, Arc-Reflection test system at the vicinity of 182nd Street & 401st Avenue, Frankfort, South Dakota.
Recent events (3)
  • — F (O) $0
  • — C (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340482793.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.