FRANKFORT, SD —
OSHA Inspection: NORTHERN ELECTRIC COOPERATIVE
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of NORTHERN ELECTRIC COOPERATIVE in 182ND STREET & 401ST AVENUE, FRANKFORT, SD 57440 (NAICS 221122). OSHA activity number 340482793.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NORTHERN ELECTRIC COOPERATIVE
- Site address
- 182ND STREET & 401ST AVENUE
- City
- FRANKFORT
- State
- SD
- ZIP
- 57440
- Mailing
- P.O. BOX 457, BATH, SD 57427
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 37
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.269 O02 I
- Issued
- Jul 30, 2015
- Abate by
- Aug 18, 2015
- Penalty
- Initial $4,900 · Current $3,900 Reduced
General-duty citation text
29 CFR 1910.269(o)(2)(i): The employer did not establish and enforce work practices for the protection of each employee from the hazards of high-voltage or high-power testing at all test areas, temporary and permanent that include, at a minimum, test area safeguarding, grounding, the safe use of measuring and control circuits, and a means providing for periodic safety checks of field test areas: (a) On or about March 11, 2015 and at times prior to that date, for the employees exposed to electrical shock hazards while operating a VON model XF 16-1280, Serial Number 610262, Arc-Reflection test system to locate an underground electrical fault at the vicinity of 182nd Street & 401st Avenue, Frankfort, South Dakota.
Recent events (3)
- — F (O) $3900
- — C (S) $4900
- — Z (S) $4900
1910.269 O04 III B
- Issued
- Jul 30, 2015
- Abate by
- Aug 11, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(o)(4)(iii)(B): During high-power testing, the employer did not protect employees from hazardous step and touch potentials that may develop during the test: (a) On or about March 11, 2015, for the employee that was shocked while locating an underground electrical fault utilizing a VON model XF 16-1280, Serial Number 610262, Arc-Reflection test system at the vicinity of 182nd Street & 401st Avenue, Frankfort, South Dakota.