CAREY, OH —
OSHA Inspection: SYNERGY PSM CORPORATION
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of SYNERGY PSM CORPORATION in 2915 COUNTY HIGHWAY 96, CAREY, OH 43316 (NAICS 561790). OSHA activity number 340486158.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SYNERGY PSM CORPORATION
- Site address
- 2915 COUNTY HIGHWAY 96
- City
- CAREY
- State
- OH
- ZIP
- 43316
- Mailing
- 62 CHERRY STREET, MOUNT CLEMENS, MI 48043
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561790
- Employees
- 25
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.147 C04 I
- Issued
- Aug 4, 2015
- Abate by
- Aug 31, 2015
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) Synergy PSM Corporation; On or about March 21, 2015, the employer failed to ensure that energy control procedures were utilized to control potentially hazardous energy sources, electrical and pneumatic, while employees performed cleaning operations inside the clean room paint booth of Continental Structural Plastics (CSP). Employees performed cleaning activities were exposed to struck by and caught between hazards in the event that ABB AS robots located inside the paint booth were to become energized.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.147 D03
- Issued
- Aug 4, 2015
- Abate by
- Aug 31, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(d)(3): All energy isolating devices that were needed to control the energy to the machine or equipment were not physically located and operated in such a manner as to isolate the machine or equipment from the energy source(s): a) Synergy PSM Corporation; On or about March 21, 2015, the employer failed to ensure that employees isolated the electrical and pneumatic energy of the ABB AS Robotic cells located inside the clean room paint booth on Continental Structural Plastics (CSP) prior to engaging in cleaning operations. Employees performing cleaning activities were exposed to struck by and caught between hazards in the event that paint robots located inside the paint booth become energized.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 F03 II D
- Issued
- Aug 4, 2015
- Abate by
- Aug 31, 2015
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.147(f)(3)(ii)(D): Each authorized employee did not affix a personal lockout or tagout device to the group lockout device before working on the machine or equipment: a) Synergy PSM Corporation; On or about March 21, 2015, the employer failed to ensure that all authorized employees engaged in cleaning operations in the clean room paint booth affixed a personal lock to either an energy isolating device or a group lockout device. Employees performing cleaning activities were exposed to struck by and caught between hazards in the event that paint robots located inside the paint booth become energized.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.147 C07 I A
- Issued
- Aug 4, 2015
- Abate by
- Aug 31, 2015
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) did not receive training in the recognition of applicable hazardous energy sources, the type and magnitude of the energy available in the workplace, and the methods and means necessary for energy isolation: a) Synergy PSM Corporation; On or about April 25, 2015 the employer failed to ensure that temporary employees who participate in group lockout procedures were trained as authorized employees prior to engaging in cleaning operations inside the clean room paint booth. Employees were exposed to struck by and caught between hazards in the event that ABB AS robots located inside the paint booth become energized.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.134 D01 III
- Issued
- Aug 4, 2015
- Penalty
- Initial $0 · Current $0
04402590H130
General-duty citation text
29 CFR 1910.134(d)(1)(iii): The employer did not identify and evaluate the respiratory hazard(s) in the workplace; including a reasonable estimate of employee exposures to respiratory hazards and identification of the contaminant's chemical state and physical form: a) Synergy PSM Corporation; On or about April 25, 2015 the employer failed to evaluate the respiratory hazards for those employees who were exposed to hazards associated with paint vapors such as, but not limited to, headaches, drowsiness, nausea, and asthmatic conditions from exposure to chemicals such as xylene, n-butyl acetate and hexamethylene diisocyanate homopolymer (HDI).
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Synergy PSM Corporation
View Synergy PSM Corporation's full OSHA safety record →
More inspections in this industry (NAICS 561790)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340486158.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.