Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: SCHNEIDER ELECTRIC, LLC

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of SCHNEIDER ELECTRIC, LLC in 2101 PELICAN ROAD, SHEPHERD, TX 77371 (NAICS 238210). OSHA activity number 340489210.

Watch Schneider Electric, LLC — free Get an email when a new federal OSHA severe-injury report for Schneider Electric, LLC is published. One employer, no account, unsubscribe in one click.
Site address
2101 PELICAN ROAD
City
SHEPHERD
State
TX
ZIP
77371
Mailing
14400 HOLLISTER RD, HOUSTON, TX 77066
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
30
Ownership type
A

1 citation on file for this inspection.

1910.269 O03 I

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $7000.00 · Current $7000.00
29 CFR 1910.269(o)(3)(i): The employer did not provide safeguarding within test areas to control access to test equipment or to apparatus under test that could become energized as part of the testing by either direct or inductive coupling and to prevent accidental employee contact with energized parts:  The employer does not ensure access to test equipment or to the apparatus under test that could become energized as part of the testing by either direct or inductive coupling is controlled and that employees do not accidently come into contact with energized parts.  This violation occurred on or about March 16, 2015, when employees performing insulation testing on top of a transformer were exposed to electrical hazards while running high voltage tests without safeguarding provided within the test areas to prevent accidental employee contact with energized parts.     Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the abatement date, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking to ensure that access to test equipment or the apparatus under test is controlled so that employees are not exposed to energized parts.
Recent events (1)
  • — Z (S) $7000

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340489210.