Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: REVERE COPPER PRODUCTS, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of REVERE COPPER PRODUCTS, INC. in 1 REVERE PARK, ROME, NY 13440 (NAICS 331421). OSHA activity number 340490226.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Revere Copper Products, INC. — free Get an email when a new federal OSHA severe-injury report for Revere Copper Products, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1 REVERE PARK
City
ROME
State
NY
ZIP
13440
Mailing
1 REVERE PARK, ROME, NY 13440
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331421
Employees
300
Ownership type
A

3 citations on file for this inspection.

1910.303 H05 V

Serious Gravity 5 1 instance 7 exposed
Issued
Jun 3, 2015
Abate by
Aug 14, 2015
Penalty
Initial $5,000 · Current $4,000 Reduced
29 CFR 1910.303(h)(5)(v) Unguarded live parts above working spaces were not maintained at elevations not les than specified in Table S-3:     a) On or about 3/24/2015, In the Mill Electric MC Room:  The main supply busses entering into the electrical room energized at a reported voltage of 15,000 volts AC was at a height of approximately seven feet, six inches at its lowest point.     Abatement certification is required for this item.
Recent events (2)
  • — I (S) $4000
  • — Z (S) $5000

1910.332 B01

Serious Gravity 10 1 instance 7 exposed
Issued
Jun 3, 2015
Abate by
Aug 14, 2015
Penalty
Initial $7,000 · Current $5,600 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    a) On or about 3/24/2015, Throughout the facility:  Employees performing electrical maintenance including, but not limited to preventative maintenance and troubleshooting, were not provided with training regarding the methods, procedures, equipment and requirements of the safety-related work practices as set forth in 1910.331 through 1910.335.    Abatement documentation is required for this item.
Recent events (2)
  • — I (S) $5600
  • — Z (S) $7000

1910.333 B02

Serious Gravity 10 2 instances 2 exposed
Issued
Jun 3, 2015
Abate by
Aug 14, 2015
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2):    a) On or about 3/24/2015, In the Mill Electric MC Room:  Employees did not de energize and lock out all energized parts inside of an electrical panel box prior to performing preventative maintenance work and the changing of a light bulb.      Abatement documentation is required for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

View Revere Copper Products, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340490226.