OSHA Inspection: REGIONAL ELECTRIC, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of REGIONAL ELECTRIC, LLC in 29 SEWELL STREET, BRUNSWICK, ME 04011 (NAICS 238210). OSHA activity number 340493659.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Regional Electric, LLC — free Get an email when a new federal OSHA severe-injury report for Regional Electric, LLC is published. One employer, no account, unsubscribe in one click.
Site address
29 SEWELL STREET
City
BRUNSWICK
State
ME
ZIP
04011
Mailing
186 SUMMER STREET, AUBURN, ME 04210
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

2 citations on file for this inspection.

1926.405 B02

Serious Gravity 5 4 instances 3 exposed
Issued
Apr 1, 2015
Abate by
Apr 9, 2015
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1926.405(b)(2): In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy:   a)  Room on southwest side of the North Commons - A cover was not provided on a permanently installed junction box which provided power to a temporary light and to a ground fault protected receptacle box mounted on a portable stand.  b)  Northeast wall of North Commons - A cover was not provided on a permanently installed receptacle box which provided power to a ground fault protected portable receptacle box.  c)  Northeast wall of North Commons - A cover was not provided on a permanently installed receptacle box which provided power to a ground fault protected portable receptacle box.  d)  Hall on south end of building - A cover was not provided on a permanently installed receptacle box which provided power to a ground fault protected receptacle box mounted on a portable stand.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

1926.403 B02

Serious Gravity 5 4 instances 3 exposed
Issued
Apr 1, 2015
Abate by
Apr 9, 2015
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:   a)  Room on southwest side of the North Commons - A non metallic sheathed cable providing power from a permanently installed junction box to a ground fault protected receptacle box mounted on a portable stand was not secured within 12 inches of the junction box and at least every 4 1/2 feet along its length.  b)  Room on southwest side of North Commons - A non metallic sheathed cable providing power from a permanently installed junction box to a temporary light was not secured within 12 inches of the junction box at least every 4 1/2 feet along its length.   c)  Northeast wall of North Commons - A non metallic sheathed cable providing power from a permanently installed receptacle box to a ground fault protected portable ground fault protected receptacle box was not secured within 12 inches of the receptacle boxes and at least every 4 1/2 feet along its length.  d)  Northeast wall of North Commons - A non metallic sheathed cable providing power from a permanently installed receptacle box to a ground fault protected portable ground fault protected receptacle box was not secured within 12 inches of the receptacle boxes and at least every 4 1/2 feet along its length.  e)  Hall on south end of building - A non metallic sheathed cable providing power from a permanently installed receptacle outlet to a ground fault protected receptacle box mounted on a portable stand was not secured within 12 inches of the junction box and at least every 4 1/2 feet along its length.