YAKIMA, WA —
OSHA Inspection: U.S. ARMY CORPS OF ENGINEERS, OMAHA DISTRICT
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of U.S. ARMY CORPS OF ENGINEERS, OMAHA DISTRICT in 970 FIRING CENTER RD, BULK FUEL POINT, YAKIMA, WA 98901 (NAICS 921190). OSHA activity number 340501485.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. ARMY CORPS OF ENGINEERS, OMAHA DISTRICT
- Site address
- 970 FIRING CENTER RD, BULK FUEL POINT
- City
- YAKIMA
- State
- WA
- ZIP
- 98901
- Mailing
- USACE CASTLE HALL, 3RD FLOOR, BUILDING 525, OFFUTT AFB, NE 68113
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 921190
- Employees
- 2
- Ownership type
- D
Citations
2 citations on file for this inspection.
1910.24 F
- Issued
- Apr 29, 2015
- Abate by
- Jun 16, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.24(f): Rise height and tread width were not uniform throughout any flight of stairs including any foundation structure used as one or more treads of the stairs: a) Fuel Bulk Point, where contract workers were exposed to fall and tripping hazards while utilizing stairways including: 1. Tank 1, where the concrete cover for the stilling tank measured 24 inches above ground level. 2. Tank 1, where the rise between the concrete cover for the stilling tank and the metal stairway measured 13 inches. 3. Tank 2, where the concrete cover for the stilling tank measured 18 inches above ground level. 4. Tank 2, where the rise between the concrete cover for the stilling tank and the metal stairway measured 13 inches.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.24 G
- Issued
- Apr 29, 2015
- Abate by
- Jun 16, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.24(g): Stairway platforms shall be no less than the width of a stairway and a minimum of 30 inches in length measured in the direction of travel: a) Fuel Bulk Point, where contract workers were exposed to fall and tripping hazards while performing job tasks on stairway platforms measuring less than 24 inches including: 1. Tank 1, where the width of the platform ranged from 15 ¾ to 16 inches due to the placement of the high level alarm canister. 2. Tank 2, where the width of the platform ranged from 14 to 18 inches due to the placement of the high level alarm canister. 3. Tank 3, where the width of the platform ranged from 15 3/4 to 16 inches due to the placement of the high level alarm canister.