OSHA Inspection: BRODER & SACHSE REAL ESTATE SERVICES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BRODER & SACHSE REAL ESTATE SERVICES, INC. in 5255 MANHATTAN RD., JACKSON, MS 39206 (NAICS 531110). OSHA activity number 340508340.

Watch Broder & Sachse Real Estate Services, INC. — free Get an email when a new federal OSHA severe-injury report for Broder & Sachse Real Estate Services, INC. is published. One employer, no account, unsubscribe in one click.
Site address
5255 MANHATTAN RD.
City
JACKSON
State
MS
ZIP
39206
Mailing
5255 MANHATTAN RD., JACKSON, MS 39206
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
531110
Employees
4
Ownership type
A

7 citations on file for this inspection.

1910.22 A01

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4500.00 · Current $200.00 Reduced
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition.    a. Maintenance Shop - On or about April 1, 2015, supplies and other material were stored haphazardly. The maintenance shop was clutter with boxes, paints and material.  Oxygen cylinders and unknown compressed gas cylinders were stored on a bottom shelf behind the refrigerator.  Oxygen cylinders should not be stored with other compressed gases and petroleum products such as paint, oil or fuels.
Recent events (2)
  • — I (O) $200
  • — Z (S) $4500

1910.304 G05

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $4500.00 · Current $4500.00
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:   a. Apartment B-2 - On or about April 1, 2015, the grounding wire that connects to the top of the water heater was not connected.  A grounding wire should have been connected at the location where the electrical wiring enters the hot water heater.
Recent events (2)
  • — I (S) $4500
  • — Z (S) $4500

1910.305 B01 I

Other-than-serious 3 instances 2 exposed
Issued
Abate by
Penalty
Initial $5400.00 · Current $200.00 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed.     a. Apartments B-2, D-3, U-2 - On or about April 1, 2015, the power cords entering the dishwasher motors and hot water heaters were not protected against abrasions and the power cord openings were not effectively closed.
Recent events (2)
  • — I (O) $200
  • — Z (S) $5400

1910.305 D02

Serious Gravity 10 3 instances 2 exposed
Issued
Abate by
Penalty
Initial $6300.00 · Current $6300.00
29 CFR 1910.305(d)(2): Panel boards were not dead front.  a. Maintenance Shop - On or about April 1, 2015, the covers were removed from the three electrical panels located on the back wall of the maintenance shop.  The live electrical parts were exposed.
Recent events (2)
  • — I (S) $6300
  • — Z (S) $6300

1910.134 C02 II

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.134(c)(2)(ii): The employer did not establish and implement those elements of a written program necessary to ensure that any employee using a respirator voluntarily was medically able to use that respirator, and that the respirator was cleaned, stored, and maintained so that its use does not present a health hazard to the user.  a. Maintenance - On or about April 1, 2015, the maintenance employees were voluntarily wearing air-purifying respirators when spraying appliance epoxy on counter tops.  The employer has not developed and implemented a respiratory protection program for voluntarily use of a respirator.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G02 I

Other-than-serious 3 instances 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets of other forms of approved enclosures, or other means listed under this provision:   a. Apartments D-3 and U-2 - On or about April 1, 2015, the electrical wiring for the hot water heater in apartment D-3, electrical wiring under the sink in apartment D-3 and the electrical wiring for the garbage disposal in apartment U-2 was spliced and capped, but the splice was not in an approved enclosure.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 G01

Other-than-serious 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $900.00 · Current $200.00 Reduced
29 CFR 1910.1200(g)(1): The employer did not have a safety data sheet for each hazardous chemical in use.    a. Maintenance - On or about April 1, 2015, safety data sheets were not available for the hazardous chemicals used by maintenance.
Recent events (2)
  • — I (O) $200
  • — Z (O) $900