OAKRIDGE, OR —
OSHA Inspection: ARMY CORPS OF ENGINEERS, HILLS CREEK DAM
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ARMY CORPS OF ENGINEERS, HILLS CREEK DAM in RIGDON ROAD, OAKRIDGE, OR 97463 (NAICS 221111). OSHA activity number 340515170.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ARMY CORPS OF ENGINEERS, HILLS CREEK DAM
- Site address
- RIGDON ROAD
- City
- OAKRIDGE
- State
- OR
- ZIP
- 97463
- Mailing
- 211 E. 7TH AVE, SUITE 480, EUGENE, OR 97401
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221111
- Employees
- 20000
- Ownership type
- D
Citations
7 citations on file for this inspection.
1910.23 C01
- Issued
- Sep 25, 2015
- Abate by
- Oct 22, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards:Note: Toeboards are only required when persons can pass, there is moving equipment or there is equipment with which falling materials could create a hazard. Hills Creek Dam- (a) The work platform used for blasting was located 10' 2" from the floor and equipment below and was not equipped with standard railings.
Recent events (1)
- — Z (S) $0
1910.219 D01
- Issued
- Sep 25, 2015
- Abate by
- Oct 22, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o): Hills Creek Dam- (a) The 5"x4" opening of the guard exposed the pulley on the air compressor, exposing employees to serious injuries.
Recent events (1)
- — Z (S) $0
1910.219 E03 I
- Issued
- Sep 25, 2015
- Abate by
- Oct 22, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(e)(3)(i): Vertical or inclined belt(s) were not enclosed by guard(s) conforming to the requirements specified at 29 CFR 1910.219(m) and (o). Hills Creek Dam- (a) The exposed V-belt was exposed and not guarded exposing employees to movement of the v-belt and in running nip points.
Recent events (1)
- — Z (S) $0
1910.215 B09
- Issued
- Sep 25, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: Hills Creek Dam- (a) The Baldor pedestal grinder's tongue guard was measured at 3/4" exposing operators to serious injuries. The Army Corps of Engineers was previously cited for a violation of this Occupational Safety and Health Standard or its equivalent standard 29 CFR 1910. 215(b)(9), which was contained in OSHA Inspection Number 941527, Citation Number 2, Item Number 3 , and was affirmed as a final order on 12 /11/2013 with respect to a work place located at, Rufus, OR. Note: Abatement certification and supporting documentation are required for these items.
Recent events (1)
- — Z (R) $0
1910.212 B
- Issued
- Sep 25, 2015
- Abate by
- Oct 22, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving: Hills Creek Dam- (a) The Baldor pedestal grinder was not bolted to the floor exposing operators to serious injuries. The Army Corps of Engineers was previously cited for a violation of this Occupational Safety and Health Standard or its equivalent standard 29 CFR 1910. 212(b), which was contained in OSHA Inspection Number 741082, Citation Number 1, Item Number 1 , and was affirmed as a final order on 04 /26/2013 with respect to a work place located at, The Dalles, OR. Note: Abatement certification and supporting documentation are required for these items.
Recent events (1)
- — Z (R) $0
1910.145 F03
- Issued
- Sep 25, 2015
- Abate by
- Oct 22, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.145(f)(3): Tags were not used as a means to prevent accidental injury or illness to employees who were exposed to hazardous or potentially hazardous conditions, equipment or operations which were out of the ordinary, unexpected or not readily apparent: Hills Creek Dam, Oil Storage Room- (a) The unexpected movement of the door counter weight, located above a stairway handrail, was not identified as to the hazardous condition.
Recent events (1)
- — Z (O) $0
1910.303 G01
- Issued
- Sep 25, 2015
- Abate by
- Oct 22, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Hills Creek Dam- (a) The CQ-5 electrical panel in the FAB shop storage area was blocked with wooden crates and other materials.
Recent events (1)
- — Z (O) $0
More inspections in this industry (NAICS 221111)
More inspections in OR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340515170.