OSHA Inspection: XTO ENERGY INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of XTO ENERGY INC in PLATFORM A, NIKISKI, AK 99635 (NAICS 211111). OSHA activity number 340530716.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch XTO Energy INC — free Get an email when a new federal OSHA severe-injury report for XTO Energy INC is published. One employer, no account, unsubscribe in one click.
Establishment
XTO ENERGY INC
Site address
PLATFORM A
City
NIKISKI
State
AK
ZIP
99635
Mailing
52260 WIK ROAD, KENAI, AK 99611
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
211111
Employees
14
Ownership type
A

4 citations on file for this inspection.

1910.305 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
May 1, 2015
Abate by
May 15, 2015
Penalty
Initial $3,400 · Current $3,400
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.  Switch Gear Room, General Electric Motor Control Center: On or about April 7, 2015 and times prior thereto, the panel marked "SPARE" had a three (3) inch diameter opening at it face. This condition exposed employees to a fire hazard and an electrical shock and burn hazard in the event of contact or ignition from the 480 volt labeled circuit.
Recent events (1)
  • — Z (S) $3400

1910.36 G02

Other-than-serious 1 instance 2 exposed
Issued
May 1, 2015
Abate by
May 8, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  Platform A, Laundry Room: On or about April 8, 2015 and times prior thereto; an exit route was restricted to 18.5 inches by the temporary storage of laundry detergents including several boxes of bleach, paper towels and a trash receptacle. This condition exposed employees to minor smoke and fume inhalation hazards.
Recent events (1)
  • — Z (O) $0

1910.147 C05 II

Other-than-serious 1 instance 4 exposed
Issued
May 1, 2015
Abate by
May 15, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(5)(ii): Lockout devices and tagout devices were not used for lockout and tagout purposes only.  Switch Gear Room/Motor Room:  On or about April 7, 2015 and times prior thereto, Lockout/Tagout devices and tags were attached to equipment that was de-energized and no longer in service. This condition exposed employees to inadequate work standards.
Recent events (1)
  • — Z (O) $0

1910.305 G01 IV B

Other-than-serious 1 instance 4 exposed
Issued
May 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:  Room 002, High Voltage Electrical Room:  On or about April 8, 2015 and at times prior thereto, a flexible cord was routed through the wall to energize a portable heater.  This condition exposed employees to minor smoke inhalation hazards in the event of flexible cord failure.
Recent events (1)
  • — Z (O) $0