HARRISBURG, PA —
OSHA Inspection: COVANTA HARRISBURG, INCORPORATED
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of COVANTA HARRISBURG, INCORPORATED in 1670 S 19TH ST, HARRISBURG, PA 17104 (NAICS 221118). OSHA activity number 340533694.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COVANTA HARRISBURG, INCORPORATED
- Site address
- 1670 S 19TH ST
- City
- HARRISBURG
- State
- PA
- ZIP
- 17104
- Mailing
- 1670 SOUTH 19TH STREET, HARRISBURG, PA 17104
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221118
- Employees
- 47
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.106 D04 I
- Issued
- Jul 8, 2015
- Penalty
- Initial $3,060 · Current $2,295 Reduced
04302590
General-duty citation text
29 CFR 1910.106(d)(4)(i): Openings from inside storage rooms were not provided with approved self-closing fire doors: (a) Paint Storage Room - The door had louvers that were covered with a filter to allow make-up air into the room, and the door did not close tightly, on or about April 10, 2015. No abatement certification or documentation required.
Recent events (2)
- — I (S) $2295
- — Z (S) $3060
1910.106 D04 IV
- Issued
- Jul 8, 2015
- Penalty
- Initial $0 · Current $0
04302590
General-duty citation text
29 CFR 1910.106(d)(4)(iv): When a mechanical exhaust system was used for an inside storage room, the exhaust was not controlled by a switch located outside of the door. The ventilating equipment and any lighting fixtures were not operated by the same switch. A pilot light was not installed adjacent to the switch if Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 degrees F (37.8 degrees C), were dispensed within the room: (a) Paint Storage Room - The control switches for both the Broan exhaust fan and light switch were located inside of the storage room and the light and fan were not operated by the same switch. A pilot light was not installed and Category 2 and 3 flammable liquids with flashpoints below 100 °F were dispensed inside the room, on or about April 10, 2015. No abatement certification or documentation required.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.106 D07 I A
- Issued
- Jul 8, 2015
- Penalty
- Initial $0 · Current $0
04302590
General-duty citation text
29 CFR 1910.106(d)(7)(i)(a): At least one portable fire extinguisher having a rating of not less than 12-B units was not located outside of, but not more than 10 feet from, the door opening into any room used for storage: (a) Paint Storage Room - A fire extinguisher was not located within 10 feet from the door of the storage room, on or about April 10, 2015. No abatement certification or documentation required.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.106 D04 III
- Issued
- Jul 8, 2015
- Penalty
- Initial $3,060 · Current $2,295 Reduced
04302590
General-duty citation text
29 CFR 1910.106(d)(4)(iii): Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 degrees F (37.8 degrees C), was not approved under subpart S of this part for Class I, Division 2 Hazardous Locations: (a) Paint Storage Room - The electrical wiring and equipment, such as the electric heater, charger, and light, was not rated for Class I, Division 2 location, on or about April 10, 2015. No abatement certification or documentation required.
Recent events (2)
- — I (S) $2295
- — Z (S) $3060
1910.106 E07 I B
- Issued
- Jul 8, 2015
- Penalty
- Initial $0 · Current $0
04302590
General-duty citation text
29 CFR 1910.106(e)(7)(i)(b): Locations where flammable vapor-air mixtures exist under normal operations were not classified Class I, Division 1 five feet in all directions from all points of vapor liberation: (a) Paint Storage Room - The employee dispensed, mixed and cleaned his paint brushes with flammable liquids inside the room and the electrical wiring and equipment, such as the electric heater, charger, and light, were not rated for Class I, Division 1 location, on or about April 10, 2015. No abatement certification or documentation required.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 A02 IX
- Issued
- Jul 8, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(ix): All lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard: (a) Paint Storage Room - The light located on the wall was not protected from accidental breakage, on or about April 10, 2015. No abatement certification or documentation required.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jul 8, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) Paint Storage Room - An extension cord was plugged into the receptacle and was used as a substitute for fixed wiring, on or about April 10, 2015. No abatement certification or documentation required.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.134 F02
- Issued
- Jul 8, 2015
- Penalty
- Initial $0 · Current $0
1591
General-duty citation text
29 CFR 1910.134(f)(2): Employee(s) using a tight-fitting facepiece respirator were not annually fit tested: (a) Covanta Energy dba Covanta Harrisburg - Employees(s) who were required to wear tight-fitting respirators were not fit tested before or on the anniversary date of the employee's previous fit test, on or about February 13, 2015. No abatement certification or documentation required.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Covanta Harrisburg, Incorporated
View Covanta Harrisburg, Incorporated's full OSHA safety record →
More inspections in this industry (NAICS 221118)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340533694.