NEW BETHLEHEM, PA —
OSHA Inspection: CLARION HOSPITAL
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of CLARION HOSPITAL in 518 PENN STREET, NEW BETHLEHEM, PA 16242 (NAICS 621910). OSHA activity number 340554112.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CLARION HOSPITAL
- Site address
- 518 PENN STREET
- City
- NEW BETHLEHEM
- State
- PA
- ZIP
- 16242
- Mailing
- 1 HOSPITAL DRIVE, CLARION, PA 16214
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 621910
- Employees
- 47
- Ownership type
- A
Citations
13 citations on file for this inspection.
1910.24 F
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $4,000 · Current $2,200 Reduced
General-duty citation text
29 CFR 1910.24(f): All treads were not reasonably slip-resistant and the nosings were not of nonslip finish: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, stairway from ambulance garage to front entrance area, on or about April 14, 2015 and times prior thereto: The rubber stair tread mats, including, but not limited to, mats located on the 3rd, 7th and 11th steps from the bottom, were not adequately affixed to the wood stairs in that the rubber mats were detaching and pulling away from the stairs.
Recent events (2)
- — I (S) $2200
- — Z (S) $4000
1910.37 A04
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, stairway from ambulance garage to front entrance area, on or about April 14, 2015 and times prior thereto: The rubber stair tread mats, including, but not limited to, mats located on the 3rd, 7th and 11th steps from the bottom, were not adequately affixed to the wood stairs in that the rubber mats were detaching and pulling away from the stairs. B.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, ambulance garage area, on or about April 14, 2015 and times prior thereto: A First Alert Carbon Monoxide and Smoke Alarm was not equipped with a battery.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.37 A02
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $3,000 · Current $1,650 Reduced
General-duty citation text
29 CFR 1910.37(a)(2): Exit routes were not arranged so that employees did not have to travel toward a high hazard area: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, southwest corner of the garage area, on or about April 14, 2015 and times prior thereto: Flammable liquids including, but not limited to, gasoline and gasoline/oil mix were stored in flammable liquid containers next to the exit door.
Recent events (2)
- — I (S) $1650
- — Z (S) $3000
1910.37 A03
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, southwest garage exit door inside, on or about April 14, 2015 and times prior thereto: Access to the exit door inside the structure was blocked by items including, but not limited to, a Craftsman lawn mower and a John Deere weed trimmer. B.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, southwest garage exit door outside, on or about April 14, 2015 and times prior thereto: Wooden timbers were laying on the ground in front of the exit door on the exterior side of the building.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.36 G04
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(4): Objects that projected into the exit route reduced the width of the exit route to less than the minimum width requirements of exit routes: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, outside southwest corner of the structure, on or about April 14, 2015 and times prior thereto: The width of the exit route outside the building which leads employees away from the building was 19.5-inches in width. The exit route was narrowed by a small shed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.36 D01
- Issued
- Jul 14, 2015
- Abate by
- Sep 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, southwest garage exit door, on or about April 14, 2015 and times prior thereto: The exit door was equipped with a pin latch device. The pin latch device was in the locked position.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.101 B
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $3,000 · Current $1,650 Reduced
General-duty citation text
29 CFR 1910.101(b): Section 5.8.4, Compressed Gas Association pamphlet P1, as adopted by 29 CFR 1910.101(b): All compressed gas cylinders in service or in storage at user locations were not secured to prevent falling or rolling: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, south side of the ambulance garage area, on or about April 14, 2015 and times prior thereto: Three large oxygen cylinders were stored along a wall between two garage doors. The oxygen cylinders were not properly secured to prevent the cylinders from tipping and/or being knocked over. The chain used to secure the cylinders was arranged in a manner in that the chain did not tightly nest and/or secure the cylinders and could allow the cylinders to fall sideways along the wall.
Recent events (2)
- — I (S) $1650
- — Z (S) $3000
1910.101 B
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.101(b): Section 5.8.2, Compressed Gas Association pamphlet P1, as adopted by 29 CFR 1910.101(b): Cylinders were stored near elevators, walkways, unprotected platform edges, and in locations where heavy moving objects can strike or fall on them: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, south side of the ambulance garage area, on or about April 14, 2015 and times prior thereto: Three large oxygen cylinders were stored along a wall between two garage doors. The oxygen cylinders were within one foot of a garage door and were potentially exposed to being struck by moving vehicles including, but not limited to, ambulances.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $3,000 · Current $1,650 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings were not provided with covers identified for the purpose, and in completed installations, each outlet box did not have a cover, faceplate, or fixture canopy: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, north side of the ambulance garage area, on or about April 14, 2015 and times prior thereto: An electrical receptacle that powers equipment including, but not limited to, a Stryker power stretcher battery charger. The cover plate for the box was broken and hanging from the battery charger's flexible cord. The receptacle box was not equipped with a cover plate. B.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, sleep quarter's, on or about April 14, 2015 and times prior thereto: An electric baseboard heater contained an electrical splice that was not enclosed by a box or cover plate. The wires and wire nuts were exposed at floor level at the base of the heater. C.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, ambulance garage area, on or about April 14, 2015 and times prior thereto: Metal electrical knockout boxes on the ceiling of the ambulance garage were not equipped with cover plates.
Recent events (2)
- — I (S) $1650
- — Z (S) $3000
1910.303 B02
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, furnace closet, on or about April 14, 2015 and times prior thereto: Two non-metallic sheath cables were spliced in a metal electrical knockout box. The electrical box was not mounted to a surface.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 A02 II
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $6,000 · Current $3,350 Reduced
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, sleep quarter's area, on or about April 14, 2015 and times prior thereto: The flexible cord for a Nighthawk carbon monoxide detector was running through a slot in the door frame. The flexible cord was frayed, exposing bare copper conductors.
Recent events (2)
- — I (S) $3350
- — Z (S) $6000
1910.305 G01 IV
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by 29 CFR 1910.305(g)(1)(iv)(A) through 29 CFR 1910.305(g)(1)(iv)(F): A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, sleep quarter's area, on or about April 14, 2015 and times prior thereto: The flexible cord for a Nighthawk carbon monoxide detector attached to building surfaces in that it was routed through a slot in the door frame and was routed through a doorway. The flexible cord was frayed, exposing bare copper conductors.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.176 B
- Issued
- Jul 14, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.176(b): Storage of material created a hazard: A.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, west side of the ambulance garage, on or about April 14, 2015 and times prior thereto: Items including, but not limited to, wooden tables and a Stryker stretcher were stacked on top of a wooden clothing rack. The items did not rest squarely on the rack and by 5-3/4 inches. B.) Clarion Hospital dba Clarion Hospital EMS Station #4, 518 Penn Street, New Bethlehem, PA 16242, ambulance garage area near stairs, on or about April 14, 2015 and times prior thereto: Items including, but not limited to, a Dirt Devil vacuum cleaner, a soiled linen bin and a basketball hoop, were stored within two feet of the front of a Reliance natural gas hot water heater / tank. The manufacturer requires a minimum of 24-inches of front clearance for servicing.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Clarion Hospital
View Clarion Hospital's full OSHA safety record →
More inspections in this industry (NAICS 621910)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340554112.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.