UNION SPRINGS, NY —
OSHA Inspection: JAY STRONGWATER, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of JAY STRONGWATER, LLC in 107 SALEM STREET, UNION SPRINGS, NY 13160 (NAICS 327112). OSHA activity number 340557644.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- JAY STRONGWATER, LLC
- Site address
- 107 SALEM STREET
- City
- UNION SPRINGS
- State
- NY
- ZIP
- 13160
- Mailing
- 107 SALEM STREET, UNION SPRINGS, NY 13160
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327112
- Employees
- 40
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.176 A
- Issued
- Jul 2, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $2,100 · Current $1,575 Reduced
General-duty citation text
29 CFR 1910.176(a): Aisle(s) and passageway(s) were not kept clear and in good repair with no obstruction across or in aisles that could create a hazard. a. Within the warehouse, on or about 04/15/15: Aisle ways were blocked with merchandise including carts and loose boxes. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $1575
- — Z (S) $2100
1910.303 B02
- Issued
- Jul 2, 2015
- Abate by
- Jul 18, 2015
- Penalty
- Initial $2,100 · Current $1,575 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling. a. On the west wall of the warehouse, on or about 04/15/15: A relocatable power tap, otherwise known as a power strip, was being used to power an industrial floor fan contrary to its listing and labeling instructions. b. In the design room, on or about 04/15/15: A relocatable power tap, otherwise known as a power strip, was being used to power an industrial fume hood contrary to its listing and labeling instructions. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $1575
- — Z (S) $2100
1910.305 G01 IV A
- Issued
- Jul 2, 2015
- Abate by
- Aug 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for fixed wiring of a structure: a. In the packing department, on or about 04/15/15: A circular saw used to build packing crates was powered by an extension cord in lieu of permanent wiring. b. In the design room, on or about 04/15/15: A heat gun used to glue gems onto art pieces was powered by an extension cord in lieu of permanent wiring. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01
- Issued
- Jul 2, 2015
- Abate by
- Jul 13, 2015
- Penalty
- Initial $2,100 · Current $1,575 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. a. Storage area between production area and design, on or about 04/15/15: Access to a circuit breaker panel was blocked by boxes and a wrought iron decorative screen. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $1575
- — Z (S) $2100
1910.303 G02 I
- Issued
- Jul 2, 2015
- Abate by
- Jul 13, 2015
- Penalty
- Initial $3,500 · Current $2,625 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: a. On the south wall of the production area, on or about 04/15/15: A circuit breaker panel was missing approximately thirteen blanks, thereby exposing its live buss bars. Abatement certification must be submitted for this item.
Recent events (2)
- — I (S) $2625
- — Z (S) $3500
1910.157 C01
- Issued
- Jul 2, 2015
- Abate by
- Jul 13, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries. a. In the area between production and design, on or about 04/15/15: Access to a mounted fire extinguisher was blocked by boxes and rolling carts. Abatement certification must be submitted for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at JAY Strongwater, LLC
View JAY Strongwater, LLC's full OSHA safety record →
More inspections in this industry (NAICS 327112)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340557644.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.