MARIETTA, OK —
OSHA Inspection: TASLER PALLET INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of TASLER PALLET INC. in 9196 PEANUT ROAD, MARIETTA, OK 73448 (NAICS 321999). OSHA activity number 340560143.
Where did this inspection happen?
- Establishment
- TASLER PALLET INC.
- Site address
- 9196 PEANUT ROAD
- City
- MARIETTA
- State
- OK
- ZIP
- 73448
- Mailing
- 9196 PEANUT ROAD, MARIETTA, OK 73448
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321999
- Employees
- 12
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.212 A01
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $1680.00 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: On or about April 15, 2015 and at times prior thereto, employees working in and around an area where an auger with unguarded blades was in operation were exposed to amputation and caught in hazards.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1910.303 G01
- Issued
- Penalty
- Initial $1600.00 · Current $960.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about April 15, 2015 and at times prior thereto, employees were exposed to electrical shock and burns due to 110 and 220 volt electrical control panels blocked by work station tables and saws set up. The electrical panels are not provided with sufficient space for maintenance and emergency shut down when necessary. Instance 1: The Panel boxes mounted on the outer wall near the main front office adjacent to pallet assembly tables on the SW side of facility. Instance 2: The panel boxes and emergency control switch located near the Ironwood cross cut saw and feed table located at far end NE side of main bldg.
Recent events (2)
- — I (S) $960
- — Z (S) $1600
1910.305 A02 I
- Issued
- Penalty
- Initial $2000.00 · Current $1200.00 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installation(s) 600 volts, nominal, or less were used in a prohibited manner. On or about April 15, 2015 and at times prior thereto, the flexible power cord set used to power the auger machine was damaged and covered with wood chips, exposing the employee to fire and electrical shock hazards.
Recent events (2)
- — I (S) $1200
- — Z (S) $2000
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $1200.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed. On or about April 15, 2015 and at times prior thereto, the employer did not ensure unused openings in a panel box mounted on the wall near the pallet assembly tables were effectively closed, exposing employees to electrical hazards.
Recent events (2)
- — I (S) $1200
- — Z (S) $2000
1910.157 C01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries. On or about April 15, 2015 and at times prior thereto, the shop area fire extinguishers were not mounted, exposing employees to hazards from fire and smoke inhalation.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 321999)
NORTH WILKESBORO, NC—2026-07-07
161501 - MILLER BEE SUPPLY, INC.
MIAMI, FL—2026-06-26
FLORIDA LUMBER COMPANY
PLATO, MN—2026-06-25
111471 - GREAT OAK EQUINE
PLATO, MN—2026-06-25
111470 - GREAT OAK EQUINE
DULUTH, MN—2026-06-23
111455 - NORTHSHORE WOOD PRODUCTS INC
More inspections in OK
MADILL, OK—2026-07-08
MID AMERICAN STEEL & WIRE CO., LLC
SEILING, OK—2026-06-26
GORE ENERGY
ADA, OK—2026-06-25
PAN AMERICA ELECTRIC , INC.
ADA, OK—2026-06-25
CITATION OIL & GAS CORPORATION
EDMOND, OK—2026-06-23
BRICK EXPERTS INC.
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340560143.