Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: TASLER PALLET INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of TASLER PALLET INC. in 9196 PEANUT ROAD, MARIETTA, OK 73448 (NAICS 321999). OSHA activity number 340560143.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tasler Pallet INC. for free Get an email when a new federal OSHA severe-injury report for Tasler Pallet INC. is published. One employer, no account, unsubscribe in one click.
Establishment
TASLER PALLET INC.
Site address
9196 PEANUT ROAD
City
MARIETTA
State
OK
ZIP
73448
Mailing
9196 PEANUT ROAD, MARIETTA, OK 73448
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321999
Employees
12
Ownership type
Private (A)

5 citations on file for this inspection.

1910.212 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 31, 2015
Abate by
Sep 23, 2015
Penalty
Initial $2,800 · Current $1,680 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  On or about April 15, 2015 and at times prior thereto, employees working in and around an area where an auger with unguarded blades was in operation were exposed to amputation and caught in hazards.
Recent events (2)
  • · I (S) $1680
  • · Z (S) $2800

1910.303 G01

Serious Gravity 5 2 instances 2 exposed
Issued
Aug 31, 2015
Penalty
Initial $1,600 · Current $960 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:   On or about April 15, 2015 and at times prior thereto, employees were exposed to electrical shock and burns  due to 110 and 220 volt electrical control panels blocked by work station tables and saws set up. The electrical panels are not provided with sufficient space for maintenance and emergency shut down when necessary.   Instance 1: The Panel boxes mounted on the outer wall near the main front office adjacent to pallet assembly tables on the SW side of facility.   Instance 2: The panel boxes and emergency control switch located near the Ironwood cross cut saw and feed table located at far end NE side of main bldg.
Recent events (2)
  • · I (S) $960
  • · Z (S) $1600

1910.305 A02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 31, 2015
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installation(s) 600 volts, nominal, or less were used in a prohibited manner.   On or about April 15, 2015 and at times prior thereto, the flexible power cord set used to power the auger machine was damaged and covered with wood chips, exposing the employee to fire and electrical shock hazards.
Recent events (2)
  • · I (S) $1200
  • · Z (S) $2000

1910.305 B01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 31, 2015
Abate by
Sep 23, 2015
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed.  On or about April 15, 2015 and at times prior thereto, the employer did not ensure unused openings in a panel box mounted on the wall near the pallet assembly tables were effectively closed, exposing employees to electrical hazards.
Recent events (2)
  • · I (S) $1200
  • · Z (S) $2000

1910.157 C01

Other-than-serious 1 instance 5 exposed
Issued
Aug 31, 2015
Abate by
Sep 23, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.    On or about April 15, 2015 and at times prior thereto, the shop area fire extinguishers were not mounted, exposing employees to hazards from fire and smoke inhalation.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 340560143.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.