OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 100 GREAT BASIN NATIONAL PARK
- City
- BAKER
- State
- NV
- ZIP
- 89311
- Mailing
- 100 GREAT BASIN NATIONAL PARK, BAKER, NV 89311
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 712190
- Employees
- 60
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.37 B01
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(1): Each exit route was not adequately lighted so that an employee with normal vision can see along the exit route: (a) Theater, Lehman Caves Visitor Center: On or about April 15, 2015 and times prior, employees were exposed to becoming entrapped in the event of a fire due to the Dual-Lite emergency lights being inoperable. (b) Kitchen, Lehman Caves Visitor Center: On or about April 15, 2015 and times prior, employees were exposed to becoming entrapped in the event of a fire due to the Dual-Lite emergency lights being inoperable.
Recent events (1)
- — Z (S) $0
1910.36 G02
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): An exit access was not at least 28 inches wide at all points: (a) Kitchen, Lehman Caves Visitor Center: On or about April 15, 2015 and times prior, employees were exposed to becoming entrapped in the event of a fire due to an the exit access from offices in the rear of the Visitor Center to the emergency exit was only approximately twenty inches wide. THE DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, GRAND CANYON FACILITY MANAGEMENT DIVISION WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 994371, CITATION 01, ITEM NUMBER 002 AND WAS AFFIRMED AS A FINAL ORDER ON FEBRUARY 4, 2015, WITH RESPECT TO A WORKPLACE LOCATED AT BUILDING 1575, SHUTTLE BUS ROAD, GRAND CANYON, ARIZONA 86023.
Recent events (1)
- — Z (R) $0
1910.303 B02
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Office Assistant Desk, Lehman Caves Visitor Center: On or about April 15, 2015 and times prior, employees are exposed to electric shock/fire by using a relocatable power tap attached to another relocatable power tap. THE DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, GRAND CANYON, VISITOR AND RESOURCE PROTECTION STATION 1 WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 992665, CITATION 01, ITEM NUMBER 005 AND WAS AFFIRMED AS A FINAL ORDER ON FEBRUARY 2, 2015, WITH RESPECT TO A WORKPLACE LOCATED AT 3 CLINIC ROAD, GRAND CANYON, ARIZONA 86023.
Recent events (1)
- — Z (R) $0
1910.305 G01 IV A
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) Theater, Lehman Caves Visitor Center: On or about April 15, 2015 and times prior, employees were exposed to electric shock/fire by using a flexible cord attached to a video display. THE DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE, GRAND CANYON, VISITOR AND RESOURCE PROTECTION STATION 1 WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 992665, CITATION 01, ITEM NUMBER 007 AND WAS AFFIRMED AS A FINAL ORDER ON FEBRUARY 2, 2015, WITH RESPECT TO A WORKPLACE LOCATED AT 3 CLINIC ROAD, GRAND CANYON, ARIZONA 86023.
Recent events (1)
- — Z (R) $0
1910.305 J02 IV
- Issued
- Aug 7, 2015
- Abate by
- Sep 2, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: (a) Janitor Closet, Lehman Caves Visitor Center: On or about April 15, 2015 and times prior, employees were exposed to electric shock due to using electrical outlet in the wet location to provide power for various electrical equipment. THE DEPARTMENT OF INTERIOR, NATIONAL PARK SERVICE CHANNEL ISLANDS NATIONAL PARK WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCUPATIONAL SAFETY AND HEALTH STANDARD, WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 899098, CITATION 01, ITEM NUMBER 004 AND WAS AFFIRMED AS A FINAL ORDER ON SEPTEMBER 11, 2013, WITH RESPECT TO A WORKPLACE LOCATED AT 1901 SPINNAKER DRIVE VENTURA, CALIFORNIA 93001