Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NAVAL POSTGRADUATE SCHOOL

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NAVAL POSTGRADUATE SCHOOL in 285 STONE ROAD QTRS. N, MONTEREY, CA 93943 (NAICS 332710). OSHA activity number 340570191.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Naval Postgraduate School — free Get an email when a new federal OSHA severe-injury report for Naval Postgraduate School is published. One employer, no account, unsubscribe in one click.
Site address
285 STONE ROAD QTRS. N
City
MONTEREY
State
CA
ZIP
93943
Mailing
285 STONE ROAD QTRS. N, MONTEREY, CA 93943
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332710
Employees
1021
Ownership type
D

7 citations on file for this inspection.

1910.36 G02

Serious Gravity 5 1 instance 2 exposed
Issued
May 11, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): An exit access was not at least 28 inches wide at all points:  Naval Postgraduate School, Building 234 Machine Shop: On or about April 15, 2015, the exit access from storage area to the exit was 17 inches wide.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Serious Gravity 5 2 instances 2 exposed
Issued
May 11, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":   Naval Postgraduate School, Building 234 Machine Shop: On or about April 15, 2015 at the loading dock, an exit door that leads to the outside of the building was not marked to state the designation of the door.
Recent events (1)
  • — Z (S) $0

1910.37 B04

Serious Gravity 1 1 instance 2 exposed
Issued
May 11, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(4): If the direction of travel to the exit or exit discharge is not immediately apparent, signs must be posted along the exit access indicating the direction of travel to the nearest exit and exit discharge. Additionally, the line-of-sight to an exit sign must clearly be visible at all times.   Naval Postgraduate School, Building 234 Machine Shop, on or about 04/15/2015: An "Exit" sign was placed behind a cast-iron pipe and was not visible.
Recent events (1)
  • — Z (S) $0

1910.212 A01

Serious Gravity 5 1 instance 1 exposed
Issued
May 11, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(1): Machine guarding was not provided to protect operator(s) and other employees from hazard(s) created by unused portion of the horizontal saw blade:   Naval Postgraduate School, Building 214 Machine Shop: The unused portion of the blade on the John Gibson horizontal saw was not guarded.
Recent events (1)
  • — Z (S) $0

1910.219 D01

Serious Gravity 10 1 instance 1 exposed
Issued
May 11, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):   Naval Postgraduate School, Building 214 Machine Shop: On or about April 15, 2015, pulleys and belts on the Bridgeport Milling  Machine were less than seven feet from the floor and were not guarded.
Recent events (1)
  • — Z (S) $0

1910.253 B04 III

Serious Gravity 5 1 instance 1 exposed
Issued
May 11, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour:  Naval Postgraduate School, Building 232 Room 29A: On or about April 15, 2015, oxygen gas cylinder and an acetylene gas cylinder were stored next to each other.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 10 1 instance 2 exposed
Issued
May 11, 2015
Abate by
Jun 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): Working space about electric equipment rated 600 volts, nominal, or less was used for storage:   Naval Postgraduate School, Building 234 Machine Shop: On or about April 15, 2015, the work space in front of the electrical panel near the loading dock doors was being used as storage.