Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NAVAL FACILITIES ENGINEERING COMMAND SOUTH WEST

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NAVAL FACILITIES ENGINEERING COMMAND SOUTH WEST in 511 GARDEN ROAD BLDG. 426, RM 011, MONTEREY, CA 93943 (NAICS 928110). OSHA activity number 340570746.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Naval Facilities Engineering Command South West — free Get an email when a new federal OSHA severe-injury report for Naval Facilities Engineering Command South West is published. One employer, no account, unsubscribe in one click.
Site address
511 GARDEN ROAD BLDG. 426, RM 011
City
MONTEREY
State
CA
ZIP
93943
Mailing
511 GARDEN ROAD BLDG. 426, RM 011, MONTEREY, CA 93943
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
74
Ownership type
D

6 citations on file for this inspection.

1910.146 C02

Serious Gravity 5 1 instance 2 exposed
Issued
May 5, 2015
Abate by
Jun 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.146(c)(2): The employer did not inform exposed employees, by posting danger signs or by any other equally effective means, of the existence and location of and the danger posed by the permit spaces.  Naval Facility Engineering Command South West, Boiler Building # 236: The employer did not post danger signs on the two boilers to warn employees of the permit required confined spaces.
Recent events (1)
  • — Z (S) $0

1910.215 A04

Serious Gravity 5 1 instance 1 exposed
Issued
May 5, 2015
Abate by
Jun 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:  Naval Facility Engineering Command South West, Public Works Building #427:  On or about April 14, 2015, the employer did not ensure that the work rest on the Baldor bench grinder was one eighth of an inch away from the wheel.
Recent events (1)
  • — Z (S) $0

1910.253 B04 III

Serious Gravity 5 1 instance 2 exposed
Issued
May 5, 2015
Abate by
Jun 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour:  Naval Facility Engineering Command South West, Public Works Building #427, Carpenter Shop: On or about April 14, 2015, oxygen gas cylinder and an acetylene gas cylinder were stored next to each other.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 1 exposed
Issued
May 5, 2015
Abate by
Jun 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listed or labeling:    Naval Facility Engineering Command South West, Public Works Building #427: On or about April 14, 2015, two metal receptacle boxes with knock outs, designed for fixed installation, were wired with black flexible cords and electrical plugs were not securely affixed to any surface.
Recent events (1)
  • — Z (S) $0

1910.303 E01 I

Serious Gravity 5 1 instance 1 exposed
Issued
May 5, 2015
Abate by
Jun 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(e)(1)(i): Electric equipment was used without the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product could be identified:  Naval Facility Engineering Command South West, Public Works Building #427: On or about April 14, 2015, there were no markings of the manufacturer's name on the two metal receptacle boxes with knock outs that were wired with black flexible cords and electrical plugs.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 1 1 instance 1 exposed
Issued
May 5, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less was used for storage:  Naval Facility Engineering Command South West, Public Works Building #427:  On or about April 14, 2015, ready access to the circuit breaker panel was blocked by storage boxes.
Recent events (1)
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340570746.