TUNKHANNOCK, PA —
OSHA Inspection: MILLWOOD INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of MILLWOOD INC. in 5530 SR 6 WEST SUITE 1, TUNKHANNOCK, PA 18657 (NAICS 321920). OSHA activity number 340574870.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MILLWOOD INC.
- Site address
- 5530 SR 6 WEST SUITE 1
- City
- TUNKHANNOCK
- State
- PA
- ZIP
- 18657
- Mailing
- 5530 SR 6 WEST SUITE 1, TUNKHANNOCK, PA 18657
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321920
- Employees
- 113
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.37 A03
- Issued
- Jun 2, 2015
- Abate by
- Jul 20, 2015
- Penalty
- Initial $3,400 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) Warehouse area: Emergency exit door #11 was covered by a screen door equipped with a closed toggle bolt, as observed on or about April 22, 2015. Abatement Certification Required.
Recent events (2)
- — I (O) $1000
- — Z (S) $3400
1910.303 B07 IV
- Issued
- Jun 2, 2015
- Abate by
- Jul 20, 2015
- Penalty
- Initial $3,400 · Current $3,400
General-duty citation text
29 CFR 1910.303(b)(7)(iv): Electrical equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: a) Line 2, Infeed 2: There was a separated conduit and damaged receptacle cover on electrical equipment exposing energized conductors to contact, as observed on or about April 22, 2015. b) IR Machine: There was a separated conduit on the conveyor motor exposing the energized conductors to contact, as observed on or about April 22, 2015. Abatement Certification Required.
Recent events (2)
- — I (S) $3400
- — Z (S) $3400
1910.305 B02 I
- Issued
- Jun 2, 2015
- Abate by
- Jul 20, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: a) Smetco: The covers of electrical boxes on two conveyor motors had been removed exposing the energized conductors, as observed on or about April 22, 2015. Abatement Certification Required.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Jun 2, 2015
- Abate by
- Jul 20, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) Line 1 Table 11: The flexible cord for the scissor lift was damaged and lacking strain relief, as observed on or about April 22, 2015. Abatement Certification Required.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Millwood INC.
View Millwood INC.'s full OSHA safety record →
More inspections in this industry (NAICS 321920)
More inspections in PA
Source