Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: APEX TOOL GROUP LLC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of APEX TOOL GROUP LLC. in 4800 KRUEGER DR., JONESBORO, AR 72401 (NAICS 332116). OSHA activity number 340577949.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Apex Tool Group LLC. — free Get an email when a new federal OSHA severe-injury report for Apex Tool Group LLC. is published. One employer, no account, unsubscribe in one click.
Site address
4800 KRUEGER DR.
City
JONESBORO
State
AR
ZIP
72401
Mailing
4800 KRUEGER DRIVE, JONESBORO, AR 72401
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332116
Employees
260
Ownership type
A

5 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 21, 2015
Abate by
Aug 4, 2015
Penalty
Initial $6,300 · Current $3,780 Reduced
OSH ACT of 1970 Section (5)(a)(1): Section 5(a)(1) of the Occupational Safety and Health Act of 1970: the employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees:  Employees operated a Skyjack DC Electric scissor lift with model number SJIII 3219 and marking N76240 to perform light removal when the overhead conveyor system transporting aluminum truck boxes began moving. An aluminum truck box struck the scissor lift, causing the lift to tip over and employees to fall to the concrete level below.
Recent events (2)
  • — I (S) $3780
  • — Z (S) $6300

1910.332 B01

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 21, 2015
Abate by
Aug 4, 2015
Penalty
Initial $6,300 · Current $3,780 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments.  Employees performed testing using a multi-meter inside of a 480 VOC energized control panel. The employer did not ensure employees were trained and familiar with safety-related work practices required in accordance with 1910.331 through 1910.335.
Recent events (2)
  • — I (S) $3780
  • — Z (S) $6300

1910.333 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 21, 2015
Abate by
Aug 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:  Employees performed testing with the use of a multi-meter inside of a 480 VOC control panel which was energized and no work practice procedures followed, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 C02

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 21, 2015
Abate by
Aug 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.333(c)(2): The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.  Employees who were not qualified persons performed testing with the use of a multi-meter on energized circuits inside of a 480 VOC control panel, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 21, 2015
Abate by
Aug 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  Employees were observed testing a 480 VOC control panel energized with the use of a multi-meter without the use of electrical protective equipment that was appropriate for parts of the body exposed, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Apex Tool Group LLC.'s full OSHA safety record →