Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BRADY AND ASSOCIATES

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BRADY AND ASSOCIATES in DOUGLAS DRIVE BUILDING 1040 MCAS, BEAUFORT, SC 29904 (NAICS 236210). OSHA activity number 340585256.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Brady and Associates — free Get an email when a new federal OSHA severe-injury report for Brady and Associates is published. One employer, no account, unsubscribe in one click.
Site address
DOUGLAS DRIVE BUILDING 1040 MCAS
City
BEAUFORT
State
SC
ZIP
29904
Mailing
PO BOX 9122, BEAUFORT, SC 29904
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236210
Employees
4
Ownership type
A

2 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 2 instances 3 exposed
Issued
Jun 29, 2015
Penalty
Initial $4,500 · Current $2,250 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a)  North end of the Job Trailer: The 120 volt Utilitech relocatable power tap model 3107, designed and listed to provide power to high concentrations of low powered loads such as computers, printers, radios, etc. was instead used to provide power to high powered loads such as a Haler Microwave; a Haler Mini Refrigerator; and a Hamilton Beach Coffee Maker.     b) North end of the Job Trailer: The 120 volt Utilitech relocatable power tap model 3107 was found to be plugged into (daisy-chained) an Innovera relocatable power tap model S9P802P6T, which was then plugged into a duplex receptacle outlet, which is a violation of its' listing.
Recent events (2)
  • — I (S) $2250
  • — Z (S) $4500

1926.404 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Jun 29, 2015
Penalty
Initial $0 · Current $0
29 CFR 1926.404(b)(2): Outlet devices. Outlet devices had an ampere rating not less than the load  being served.  a) North end of the Job Trailer: A 120 volt six outlet Utilitech relocatable power tap was used to provide power to a Haler mini refrigerator (8.3 amps); a Haler microwave oven (12 amps); and a Hamilton Beach coffee maker (8 amps) with a total amperage of  23.3, which is a larger amperage than the power tap's 15 amp capacity.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340585256.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.