OSHA Inspection: BONUS ELECTRIC COMPANY, L.L.C.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of BONUS ELECTRIC COMPANY, L.L.C. in 1000 S. CLARK ST., CHICAGO, IL 60605 (NAICS 238210). OSHA activity number 340590801.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bonus Electric Company, L.L.C. — free Get an email when a new federal OSHA severe-injury report for Bonus Electric Company, L.L.C. is published. One employer, no account, unsubscribe in one click.
Site address
1000 S. CLARK ST.
City
CHICAGO
State
IL
ZIP
60605
Mailing
112 MAIN ST., LEMONT, IL 60439
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
5
Ownership type
A

3 citations on file for this inspection.

1926.405 A02 II B

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 23, 2015
Penalty
Initial $1,600 · Current $1,120 Reduced
29 CFR 1926.405(a)(2)(ii)(B): Branch circuits shall originate in a power outlet or panelboard. Conductors shall be run as multiconductor cord or cable assemblies or open conductors, or shall be run in raceways. All conductors shall be protected by overcurrent devices at their ampacity. Runs of open conductors shall be located where the conductors will not be subject to physical damage, and the conductors shall be fastened at intervals not exceeding 10 feet (3.05 m). No branch-circuit conductors shall be laid on the floor. Each branch circuit that supplies receptacles or fixed equipment shall contain a separate equipment grounding conductor if the branch circuit is run as open conductors.  a.  On or about April 28, 2015 - at the above addressed jobsite, the electrical cable was not protected from damage when exiting the temporary power panels on the fifteenth (15) floor, thereby exposing the employees and subcontractor employees to hazards associated with electrical shock.
Recent events (2)
  • — I (S) $1120
  • — Z (S) $1600

1926.416 E01

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 23, 2015
Penalty
Initial $0 · Current $0
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables shall not be used.  On or about April 28, 2015 - at the above addressed jobsite, a damaged electrical cord was used to supply power from the 15th floor to the 16th floor, thereby exposing the employees and subcontractor employees to hazards associated with electrical shock.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 B01

Serious Gravity 1 2 instances 115 exposed
Issued
Jun 23, 2015
Penalty
Initial $1,200 · Current $840 Reduced
29 CFR 1926.405(b)(1): Conductors entering boxes, cabinets, or fittings. Conductors entering boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. Unused openings in cabinets, boxes, and fittings shall also be effectively closed.  a.  On or about April 28, 2015 - at the above addressed jobsite, On the 4th floor, unused openings in two separate electrical panels were not effectively closed, thereby exposing employees and subcontractor employees to electrical hazards.  b.  On or about April 28, 2015 - at the above addressed jobsite, On the 8th floor, an unused opening in the electrical panel was not effectively closed, thereby exposing employees and subcontractor employees to electrical hazards.
Recent events (2)
  • — I (S) $840
  • — Z (S) $1200