BEAUMONT, TX —
OSHA Inspection: MARTIN OPERATING PARTNERSHIP LLP
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of MARTIN OPERATING PARTNERSHIP LLP in #1 GULF STATES ROAD, BEAUMONT, TX 77704 (NAICS 325311). OSHA activity number 340610815.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MARTIN OPERATING PARTNERSHIP LLP
- Site address
- #1 GULF STATES ROAD
- City
- BEAUMONT
- State
- TX
- ZIP
- 77704
- Mailing
- P.O. BOX 6567, BEAUMONT, TX 77725
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325311
- Employees
- 1200
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.119 D03 I B
- Issued
- Oct 27, 2015
- Abate by
- Nov 29, 2015
- Penalty
- Initial $5,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process. On May 5, 2015 and at prior times and possibly at times subsequent thereto, at the Martin Operating Partnership, L.P. Neches Terminal, in Beaumont, Texas, the employer did not ensure that the process safety information depicted in P&IDs was up-to-date and accurate for the Ammonia transfer process when: (a) The employer P&ID NEC-02958 Rev G did not include detail to allow valves and instruments to be positively identified. (b) The employer P&ID NEC-02962 Rev H did not provide information to represent pumps P-108B and P-108C that are part of the ammonia process. (c) The employer P&ID NEC-02963 Rev G showed a pressure vessel PV-521 with maximum pressure of 250 psi being protected against over pressure by PSV-050 with set pressure at 270 psi. (d) The employer P&ID NEC-02963 Rev G did not show a relief pressure for PSV-053 (e) The employer P&ID NEC-02967 Rev F did not provide accurate and complete information to represent Ammonia barge loading pumps P-106A and P-106B. (f) The employer P&ID NEC-02968 Rev E did not include information to identify pressure vessels in the process. (g) On the employer P&ID NEC-02969 Rev E, process safety information for V-4 is not included and several instruments on the diagram do not have identifying information. (h) On the employer P&ID NEC-02972 Rev F, process safety information on the diagram is for equipment not represented on the diagram and there is no information on the diagram that allows identification of the PSV. (i) On the employer P&ID NEC-02973 Rev F, process safety information on the diagram is for equipment not represented on the diagram and there are several instruments that have no identifying detail included on the diagram. (j) The employer P&ID NEC-02976 Rev D did not provide information to positively identify PSVs associated with the Oil Separator V-4 and Oil Cooler V-7. (k) The employer P&ID NEC-02977 Rev D did not provide information to positively identify PSVs associated with V-5 and V-8. (l) The employer P&ID NEC-02978 Rev D did not provide information to positively identify PSV associated with V-9. (m) The employer P&ID NEC-02979 Rev D did not provide information to positively identify and verify the PSVs associated with V3 and does not include information to identify instruments on the diagram. (n) The employer P&ID NEC-02982 Rev F did not provide identification numbers for several instruments in the control system for the ammonia heater. (o) The employer P&ID NEC-02983 Rev E did not provide identification numbers for several instruments in the control system for the ammonia heater. (p) The employer P&ID NEC-02988 Rev A did not provide identification number or relief pressure detail for the PSV shown in the diagram.
Recent events (2)
- — I (S) $0
- — Z (S) $5000
1910.119 J04 I
- Issued
- Oct 27, 2015
- Abate by
- Feb 3, 2016
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment On or around June 3, 2015 and at times prior and possibly at times subsequent thereto, at the Martin Operating Partnership, L.P. Neches Terminal in Beaumont, Texas the employer did not perform inspections on process equipment when: (a) The employer did not inspect piping associated with ammonia refrigeration compressors and failed to observe that relief valves PSV-115 and PSV-116 in the piping system were overdue for replacement. (b) The employer allowed pressure relief valves to remain in service for more than five years in the ammonia refrigeration piping system. .
Recent events (2)
- — I (O) $7000
- — Z (S) $7000
1910.119 J05
- Issued
- Oct 27, 2015
- Abate by
- Nov 29, 2015
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that are outside acceptable limits (defined by the process safety information in paragraph (d) of this section) before further use or in a safe and timely manner when necessary means are taken to assure safe operation. On June 3, 2015 and at prior times and possibly at times subsequent thereto, at the Martin Operating Partnership, L. P. Neches Terminal in Beaumont, Texas, the employer did not correct deficiencies in equipment that were outside acceptable limits before further use or in a safe and timely manner and did not ensure necessary means were taken to ensure safe operation of the process when: (a) The employer allowed pressure relief valves to remain in service for more than five years in the ammonia refrigeration piping system. (b) External coatings of piping in the ammonia transfer system were not maintained. (C) Process valves were installed in operating piping systems but did not have handles on the valves for operation (valves cannot be operated properly to control the process without handles or valve operators installed).
Recent events (2)
- — I (S) $0
- — Z (S) $7000
More inspections at Martin Operating Partnership LLP
View Martin Operating Partnership LLP's full OSHA safety record →
More inspections in this industry (NAICS 325311)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340610815.