OSHA Inspection: PUBLIC ELECTRIC CONSTRUCTION CO.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of PUBLIC ELECTRIC CONSTRUCTION CO. in 1000 N. MILWAUKEE AVE., WHEELING, IL 60090 (NAICS 238210). OSHA activity number 340620178.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Public Electric Construction CO. — free Get an email when a new federal OSHA severe-injury report for Public Electric Construction CO. is published. One employer, no account, unsubscribe in one click.
Site address
1000 N. MILWAUKEE AVE.
City
WHEELING
State
IL
ZIP
60090
Mailing
415 HARVESTER CT., WHEELING, IL 60090
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

6 citations on file for this inspection.

1926.20 B02

Other-than-serious 3 instances 7 exposed
Issued
Jun 30, 2015
Penalty
Initial $2,400 · Current $1,680 Reduced
29 CFR 1926.20(b)(2): The employer did not initiate and maintain programs which provided for frequent and regular inspections of the job site, materials and equipment to be made by a competent person(s):    a) On or about May 7, 2015, employees were exposed to electrical hazards that were not identified and corrected during regular inspections of temporary electrical installations.    No abatement certification or documentation required for this violation.
Recent events (2)
  • — I (O) $1680
  • — Z (S) $2400

1926.416 E01

Deleted Serious Gravity 5 1 instance 7 exposed
Issued
Jun 30, 2015
Penalty
Initial $0 · Current $0
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables were used:    a) On or about May 7, 2015, employees were exposed to electrical hazards caused by an extension cord that was hardwired into a circuit breaker panel which had numerous cuts and melted spots along its length.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 B01

Serious Gravity 5 1 instance 7 exposed
Issued
Jun 30, 2015
Penalty
Initial $2,400 · Current $1,680 Reduced
29 CFR 1926.405(b)(1): Openings in boxes, cabinets, and fittings through which conductors entered were not effectively closed:     a) On or about May 7, 2015, employees were exposed to electrical shock from a circuit breaker panel that did not have a dead front or cover on it.
Recent events (2)
  • — I (S) $1680
  • — Z (S) $2400

1926.405 D

Deleted Serious Gravity 5 1 instance 7 exposed
Issued
Jun 30, 2015
Penalty
Initial $0 · Current $0
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front:   a) On or about May 7, 2015, employees were exposed to electrical shock and burns from a circuit breaker panel that did not have a cover on it.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 G01 II

Deleted Serious Gravity 5 1 instance 7 exposed
Issued
Jun 30, 2015
Penalty
Initial $2,400 · Current $0 Reduced
29 CFR 1926.405(g)(1)(ii): Flexible cord was not equipped with an attachment plug and energized from a receptacle outlet when used as permitted in 29 CFR 1926.405(g)(1)(i) [C], [F], or [H]:    a) On or about May 7, 2015, employees were exposed to electrical hazards caused by an extension cord supplying power tools that was hardwired into a circuit breaker panel.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2400

1926.405 G02 IV

Other-than-serious 1 instance 7 exposed
Issued
Jun 30, 2015
Penalty
Initial $0 · Current $1,000
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws:       a) On or about May 7, 2015, employees were exposed to electrical hazards caused by an extension cord that was hardwired into a circuit breaker panel without any type of strain relief to prevent tension being applied to the terminal screws on the buss bar and circuit breaker.