FAIRMONT, WV —
OSHA Inspection: ABM GOVERNMENT SERVICES LLC
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of ABM GOVERNMENT SERVICES LLC in 1000 GALLIHER DRIVE, FAIRMONT, WV 26554 (NAICS 811310). OSHA activity number 340629476.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ABM GOVERNMENT SERVICES LLC
- Site address
- 1000 GALLIHER DRIVE
- City
- FAIRMONT
- State
- WV
- ZIP
- 26554
- Mailing
- 12040 INDIAN CREEK COURT, BELTSVILLE, MD 20705
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811310
- Employees
- 3
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.332 B01
- Issued
- Oct 13, 2015
- Abate by
- Oct 23, 2015
- Penalty
- Initial $5,000 · Current $5,000
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: (a) NOAA facility, Fairmont, WV: Employees that were required to do electrical equipment isolation were not provided training on the applicable safety related work practices listed under 29 CFR 1910.331 through 1910.335 including, but not limited to, the necessary PPE to be worn when racking the 15 kV circuit breakers in and out while standing within the arc flash boundary as determined on May 12, 2015. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $5000
- — C (S) $5000
- — Z (S) $5000
1910.332 B02
- Issued
- Oct 13, 2015
- Abate by
- Oct 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.332(b)(2): Employees, who were not qualified persons, were not trained in and familiar with the electrically related safety practices not specifically addressed by 29 CFR 1910.331 through 29 CFR 1910.335, but which were necessary for their safety: (a) CPS building, NOAA facility, Fairmont, WV: Employees that were responsible for racking out the 15 kV MV-1 Switchgear were not provided training on arc flash hazards associated with racking a circuit breaker in or out as determined on May 12, 2015. (b) CPS building, NOAA facility, Fairmont, WV: Employees that were responsible for racking out the 15 kV MV-1 Switchgear were not provided training on the arc flash labeling that was present on electrical equipment as determined on May 12, 2015. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $0
- — C (S) $0
- — Z (S) $0
1910.335 A01 V
- Issued
- Oct 13, 2015
- Abate by
- Oct 23, 2015
- Penalty
- Initial $5,000 · Current $5,000
General-duty citation text
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face: (a) CPS building, NOAA facility, Fairmont, WV: Employees that were inside the arc flash boundary were not required to wear eye and face PPE to protect against an arc flash while racking the 15 kV MV-1 Switchgear circuit breaker in and out as determined on May 12, 2015. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $5000
- — C (S) $5000
- — Z (S) $5000
1910.335 A01 I
- Issued
- Oct 13, 2015
- Abate by
- Oct 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: (a) CPS building, NOAA facility, Fairmont, WV: Employees that were inside the arc flash boundary were not required to wear protective gloves to protect against an arc flash while racking the 15 kV MV-1 Switchgear circuit breaker in and out as determined on May 12, 2015. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $0
- — C (S) $0
- — Z (S) $0
1910.132 A
- Issued
- Oct 13, 2015
- Abate by
- Oct 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered: (a) CPS building, NOAA facility, Fairmont, WV: Employees that were inside the arc flash boundary were not required to wear head protection, hearing protection, and Flame Resistant clothing to protect against an arc flash explosion while racking the 15 kV MV-1 Switchgear circuit breaker in and out as determined on May 12, 2015. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $0
- — C (S) $0
- — Z (S) $0
1910.132 D01
- Issued
- Oct 13, 2015
- Abate by
- Oct 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE): (a) CPS building, NOAA facility, Fairmont, WV: The employer had not assessed the workplace to determine the PPE needed for employees that rack the 15 kV MV-1 Switchgear circuit breaker in and out in that employees stand inside the arc flash boundary while racking the breaker and were not wearing eye and face PPE, head PPE, and hand PPE to protect against an arc flash explosion as determined on May 12, 2015. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $0
- — C (S) $0
- — Z (S) $0
1910.333 B02 II A
- Issued
- Oct 13, 2015
- Abate by
- Oct 23, 2015
- Penalty
- Initial $5,000 · Current $5,000
General-duty citation text
29 CFR 1910.333(b)(2)(ii)(A): Safe procedures for deenergizing circuits and equipment were not determined before circuits and equipment were de-energized: (a) NOAA facility, Fairmont, WV: Safe procedures were not developed prior to the de-energizing of all parts of a 15 kV electrical cabinet, as determined on May 12, 2015. ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — F (O) $5000
- — C (S) $5000
- — Z (S) $5000
More inspections at ABM Government Services LLC
View ABM Government Services LLC's full OSHA safety record →
More inspections in this industry (NAICS 811310)
More inspections in WV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340629476.