Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SOCIAL SECURITY ADMINISTRATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SOCIAL SECURITY ADMINISTRATION in 102 GARRIDO MORALES, FAJARDO, PR 00738 (NAICS 923130). OSHA activity number 340649904.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Social Security Administration — free Get an email when a new federal OSHA severe-injury report for Social Security Administration is published. One employer, no account, unsubscribe in one click.
Site address
102 GARRIDO MORALES
City
FAJARDO
State
PR
ZIP
00738
Mailing
102 GARRIDO MORALES, FAJARDO, PR 00738
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
923130
Employees
10
Ownership type
D

4 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 5 instances 1 exposed
Issued
Jul 30, 2015
Abate by
Aug 25, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling:    On or about 05/19/15, at 102 Garrido Morales, Fajardo, PR, in the IT area, five (5) relocatable power taps were not directly connected to a permanently installed branch circuit receptacle.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 3 instances 10 exposed
Issued
Jul 30, 2015
Abate by
Aug 25, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear:  a) On or about 05/19/15, at 102 Garrido Morales, Fajardo, PR, in the water cooler area, an electrical outlet box was not covered.  b) On or about 05/19/15, at 102 Garrido Morales, Fajardo, PR, in the maintenance room located in the reception area, an electrical outlet box was not covered.  c) On or about 05/19/15, at 102 Garrido Morales, Fajardo, PR, in the reception area, an electrical outlet box was not covered.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 1 1 instance 10 exposed
Issued
Jul 30, 2015
Abate by
Aug 25, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed:  On or about 05/19/15, at 102 Garrido Morales, Fajardo, PR,, in the reception area, a circuit breaker panel had unused openings not covered.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV E

Serious Gravity 1 1 instance 10 exposed
Issued
Jul 30, 2015
Abate by
Aug 25, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(E): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used where concealed behind building walls, ceilings, or floors:   On or about 05/19/15, at 102 Garrido Morales, Fajardo, PR, in the reception area, a flexible cord was concealed behind a building wall.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

View Social Security Administration's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340649904.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.