BRONX, NY —
OSHA Inspection: ELITE HOME IMPROVEMENT AND CONSTRUCTION, INC.
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of ELITE HOME IMPROVEMENT AND CONSTRUCTION, INC. in 2477 3RD AVE., BRONX, NY 10451 (NAICS 238190). OSHA activity number 340657659.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ELITE HOME IMPROVEMENT AND CONSTRUCTION, INC.
- Site address
- 2477 3RD AVE.
- City
- BRONX
- State
- NY
- ZIP
- 10451
- Mailing
- 93-41 222ND STREET, APT 2C, QUEENS VILLAGE, NY 11428
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238190
- Employees
- 4
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.404 B01 I
- Issued
- Jun 26, 2015
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites: On or about: 5/26/15 Location: 2477 3rd Ave. Bronx NY 10451 a) Employees worked with fireproofing equipment and extension cords that were not protected by a ground fault circuit interrupter (GFCI).
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
1926.404 E01 I
- Issued
- Jun 26, 2015
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1926.404(e)(1)(i): Conductors rated 600 volts, nominal, or less did not have sufficient ampacity to carry the load: On or about: 5/26/15 Location: 2477 3rd Ave. Bronx NY, 10451 a) Employees were working with an IMER Small 50 fireproof sprayer which has an ampacity of 18 amps. The 15 amp orange extension cord used to energize the equipment did not have the ampacity to carry the load needed.
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
1926.405 G02 IV
- Issued
- Jun 26, 2015
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws: On or about: 5/26/15 Location: 2477 3rd Ave. Bronx NY 10451 a) Employees worked with an orange extension cord to energize an IMER Small 50 fireproofing sprayer. The cord did not have strain relief on the female plug end.
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
1926.416 E01
- Issued
- Jun 26, 2015
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1926.416(e)(1): Worn or frayed electric cords or cables were used: On or about: 5/26/15 Location: 2477 3rd Ave. Bronx NY, 10451 a) Employees worked with an orange extension cord to power fireproofing equipment. The cord was damaged and worn.
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
More inspections in this industry (NAICS 238190)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340657659.