Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TONY'S FINER FOODS ENTERPRISES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of TONY'S FINER FOODS ENTERPRISES, INC. in 4137 N. ELSTON, CHICAGO, IL 60618 (NAICS 445110). OSHA activity number 340658012.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tony'S Finer Foods Enterprises, INC. — free Get an email when a new federal OSHA severe-injury report for Tony'S Finer Foods Enterprises, INC. is published. One employer, no account, unsubscribe in one click.
Site address
4137 N. ELSTON
City
CHICAGO
State
IL
ZIP
60618
Mailing
4137 N. ELSTON, CHICAGO, IL 60618
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
445110
Employees
120
Ownership type
A

5 citations on file for this inspection.

1910.303 B06

Serious Gravity 5 2 instances 14 exposed
Issued
Aug 12, 2015
Penalty
Initial $5,100 · Current $3,060 Reduced
29 CFR 1910.303(b)(6): Conductors or equipment were located in damp or wet locations were not identified for use in that operating environment:  a) Meat Cutting Department- The employer failed to ensure that all electrical equipment, such as the twist locks used to power the bandsaws in the Meat Cutting Department, were identified for use in damp or wet locations.  These twist locks showed signs of corrosion and were wet when examined.   No abatement certification or documentation is required for this item.
Recent events (2)
  • — I (S) $3060
  • — Z (S) $5100

1910.305 E01

Serious Gravity 5 1 instance 4 exposed
Issued
Aug 12, 2015
Penalty
Initial $5,100 · Current $3,060 Reduced
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:  a) Meat Cutting Department-  The employer failed to ensure all boxes and fittings in damp or wet locations, such as the outlet next to the Hamburger Machine, were installed to prevent moisture and water from entering and accumulating.  This box may have been originally installed to be weatherproof, but the connecting screws and box itself showed signs of corrosion and it was no longer maintained in a weatherproof condition to prevent water from entering and accumulating.  In addition, this outlet was not equipped with ground fault circuit interruption protection.  No abatement certification or documentation is required for this item.
Recent events (2)
  • — I (S) $3060
  • — Z (S) $5100

1910.305 G01 IV B

Serious Gravity 1 1 instance 25 exposed
Issued
Aug 12, 2015
Penalty
Initial $2,550 · Current $1,530 Reduced
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:  a) Grocery Area- The employer failed to ensure that flexible cords were not run through holes in walls and through the ceiling.  A temporary wiring extension cord was run through a wall hole and through the ceiling from the electrical closet to a Portable Freezer by the Dairy Case.    No abatement certification or documentation is required for this item.
Recent events (2)
  • — I (S) $1530
  • — Z (S) $2550

1910.305 G01 IV C

Serious Gravity 1 1 instance 25 exposed
Issued
Aug 12, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were used where run through doorways, windows, or similar openings.  a) Grocery Area- The employer failed to ensure that flexible cords were not run through doorways.  A cord was run through a doorway to supply power to a Portable Freezer by the Dairy Case.    No abatement certification or documentation is required for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 14 exposed
Issued
Aug 12, 2015
Penalty
Initial $5,100 · Current $3,060 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  a) Meat Cutting Department- The employer failed to ensure that flexible cords, such as the flexible cord running to the DPS-4600 Labeler Printing Scale, were supplied with strain relief to prevent pull from being transferred to joints and terminal screws.    No abatement certification or documentation is required for this item.
Recent events (2)
  • — I (S) $3060
  • — Z (S) $5100

View Tony'S Finer Foods Enterprises, INC.'s full OSHA safety record →