CHALFONT, PA —
OSHA Inspection: QUAD/GRAPHICS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of QUAD/GRAPHICS, INC. in 4371 COUNTY LINE RD, CHALFONT, PA 18914 (NAICS 323111). OSHA activity number 340659564.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- QUAD/GRAPHICS, INC.
- Site address
- 4371 COUNTY LINE RD
- City
- CHALFONT
- State
- PA
- ZIP
- 18914
- Mailing
- 4371 COUNTY LINE RD, CHALFONT, PA 18914
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323111
- Employees
- 500
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.303 B01
- Issued
- Sep 23, 2015
- Penalty
- Initial $4,250 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees: a) Quad Graphics Inc., Baler / Shredder Room - On or about May 27, 2015, the metal electric box of a phone buzzer was disconnected from the wall, hanging from the power cord, and incorrectly wired to the power circuit. b) Quad Graphics Inc., Baler / Shredder Room - On or about May 27, 2015, a metal electric switch box was disconnected from the wall, separated from the conduit connections, and hanging from the inner wiring electrical cords. c) Quad Graphics Inc., Baler / Shredder Room - On or about May 27, 2015, a metal electric key switch box was disconnected from the wall. d) Quad Graphics Inc., Baler / Shredder Room - On or about May 27, 2015, a four inch square metal knock out type box with an alarm bell was disconnected from the wall, separated from the conduit connections, and hanging from the inner wiring electrical cords.
Recent events (3)
- — F (S) $0
- — C (S) $4250
- — Z (S) $4250
1910.305 A01 I
- Issued
- Sep 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(1)(i): Metal raceways, cable trays, cable armor, cable sheath, enclosures, frames, fittings, and noncurrent-carrying parts that are to serve as grounding conductors, with or without the use of supplementary equipment grounding conductors, were not effectively bonded where necessary to ensure electrical continuity and did not have the capacity to conduct safely any fault current likely to have been imposed on them: a) Quad Graphics Inc., Baler / Shredder Room - On or about May 27, 2015, the metal electric box of a phone buzzer was disconnected from the wall, hanging from the power cord, and not effectively bonded to ensure electrical continuity. b) Quad Graphics Inc., Baler / Shredder Room - On or about May 27, 2015, a metal electric switch box was disconnected from the wall, separated from the conduit connections, hanging from the inner wiring electrical cords and was not effectively bonded to ensure electrical continuity.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
More inspections at Quad/Graphics, INC.
View Quad/Graphics, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 323111)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340659564.