PHILADELPHIA, PA —
OSHA Inspection: RUE ELECTRIC, INC.
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of RUE ELECTRIC, INC. in 1720 FAIRMOUNT AVE, PHILADELPHIA, PA 19130 (NAICS 238210). OSHA activity number 340664572.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RUE ELECTRIC, INC.
- Site address
- 1720 FAIRMOUNT AVE
- City
- PHILADELPHIA
- State
- PA
- ZIP
- 19130
- Mailing
- 4935 NATIONAL ST, PHILADELPHIA, PA 19135
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 5
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.403 I02
- Issued
- Jun 19, 2015
- Penalty
- Initial $2,800 · Current $2,800
General-duty citation text
29 CFR 1926.403(i)(2): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures: a.) 1720 Fairmont Street, Philadelphia, PA. - The main energized (120/240 volt) electrical circuit breaker panel had missing circuit breakers. The energized buss bar was exposed. This hazard exposed the employees to shock/electrocution hazards, on or about May 28, 2015.
Recent events (1)
- — Z (S) $2800
1926.403 I01
- Issued
- Jun 19, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(i)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. a) 1720 Fairmont Ave - Construction debris, was located in front of the main electrical panel, causing a trip hazard and exposing the employees to electrical hazards. Observed on or about May 28, 2015.
Recent events (1)
- — Z (S) $0
1926.405 B01
- Issued
- Jun 19, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(b)(1): Conductors entering boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. Unused openings in cabinets, boxes, and fittings shall also be effectively closed: a.) 1720 Fairmont Ave. Philadelphia, PA - Energized (120/240 volts) conductors entering circuit breaker panel were not protected from abrasion, and unused openings in cabinets, boxes were not effectively closed as required thus exposing the employee to shock/electrical hazards. This condition was observed on or about May 28, 2015.
Recent events (1)
- — Z (S) $0
1926.405 A02 II E
- Issued
- Jun 19, 2015
- Penalty
- Initial $2,800 · Current $2,800
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(E): Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage: a) 1720 Fairmont Ave., Philadelphia, PA - The employer did not ensure that the energized (120 volts) light socket for temporary lighting was guarded against accidental contact, no light bulb installed nor was a guard installed thus exposing the employees to shock/electrocution hazards. This condition was observed on or about May 28, 2015.
Recent events (1)
- — Z (S) $2800
More inspections at RUE Electric, INC.
View RUE Electric, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340664572.