BOISE, ID —
OSHA Inspection: ELECTRIC AUTHORITY, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ELECTRIC AUTHORITY, INC. in INGALLS & ELLSWORTH, GOWEN FIELD, BOISE, ID 83705 (NAICS 238210). OSHA activity number 340669175.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ELECTRIC AUTHORITY, INC.
- Site address
- INGALLS & ELLSWORTH, GOWEN FIELD
- City
- BOISE
- State
- ID
- ZIP
- 83705
- Mailing
- 16390 HWY 78, MELBA, ID 83641
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 2
- Ownership type
- A
Citations
3 citations on file for this inspection.
1903.19 C01
- Issued
- Sep 29, 2015
- Abate by
- Nov 17, 2015
- Penalty
- Initial $340 · Current $340
General-duty citation text
29 CFR 1903.19(c)(1): The employer did not certify to OSHA within 10 calendar days after the abatement date that each cited violation had been abated: a) Jobsite at Ingalls & Ellsworth, Gowen Field: The employer, Electrical Authority, Inc., failed to provide certification of corrective action for inspection number 1066917, item 1a and 1b. The date by which these violations were to be corrected was July 24, 2015.
Recent events (1)
- — Z (O) $340
1926.405 D
- Issued
- Jun 29, 2015
- Abate by
- Jul 24, 2015
- Penalty
- Initial $1,700 · Current $1,700
General-duty citation text
29 CFR 1926.405(d): Panel boards having exposed live parts were not located in permanently dry locations and accessible only to qualified persons: a) Building 669 main electrical panels East wall: On or about 5-18-2015, employees were exposed to live parts from D and ED-1, 208 3 phase panel boards whose dead front switch covers had been removed to allow temporary flexible cables to be wired directly into the electrical panels, and were not locked or guarded from access by only qualified persons . Note: Abatement certification is required for this item.
Recent events (1)
- — Z (S) $1700
1926.405 G01 II
- Issued
- Jun 29, 2015
- Abate by
- Jul 24, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(g)(1)(ii): Flexible cord was not equipped with an attachment plug and energized from a receptacle outlet when used as permitted in 29 CFR 1926.405(g)(1)(i) [C], [F], or [H]: a) Building 669 main electrical panels East wall: On or about 5-18-2015, employees were exposed to temporary flexible power cords that were wired directly into the electrical panels, instead of through a knockout and using a pigtail and receptacle for connection. Note: Abatement certification is required for this item.
Recent events (1)
- — Z (S) $0
More inspections in this industry (NAICS 238210)
More inspections in ID
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340669175.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.