VALLEY CENTER, CA —
OSHA Inspection: W.E. O'NEIL CONSTRUCTION COMPANY OF CALIFORNIA
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of W.E. O'NEIL CONSTRUCTION COMPANY OF CALIFORNIA in GIFT SHOP RENOVATION PROJECT AT HARRAH'S RESORT SOUTHERN CALIFORNIA 777 HARRAHS RINCON WAY, RINCON BAND OF LUESENO INDIANS TRIBAL LAND, VALLEY CENTER, CA 92082 (NAICS 236220). OSHA activity number 340669258.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- W.E. O'NEIL CONSTRUCTION COMPANY OF CALIFORNIA
- Site address
- GIFT SHOP RENOVATION PROJECT AT HARRAH'S RESORT SOUTHERN CALIFORNIA 777 HARRAHS RINCON WAY, RINCON BAND OF LUESENO INDIANS TRIBAL LAND
- City
- VALLEY CENTER
- State
- CA
- ZIP
- 92082
- Mailing
- 9485 HAVEN AVENUE, RANCHO CUCAMONGA, CA 91730
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236220
- Employees
- 70
- Ownership type
- A
Citations
1 citation on file for this inspection.
1926.417 B
- Issued
- Jun 23, 2015
- Abate by
- Jun 29, 2015
- Penalty
- Initial $1,785 · Current $0 Reduced
General-duty citation text
29 CFR 1926.417(b): Equipment and circuits. Equipment or circuits that were deenergized were not rendered inoperative and did not have tags attached at all points where such equipment or circuits can be energized: In the room in back of the gift shop area, there were no tags on the 20 ampere circuit breakers 8 and 20 that were in the off position and that had been used to supply power to the wires in receptacle boxes in the gift shop area. The boxes were about 2 inches wide by 3 inches high and bottoms were about 23 inches above the floor. The wires were removed from the breakers and wire nuts were on the wires rolled up in the receptacle boxes. There were no covers or receptacles on the boxes. Harrah's Resort electrical maintenance staff had access to the panel and can reattach wires to the breakers in the panel. The door to the room and the door on the panel were not locked. W.E. O'Neil, the general contractor onsite, hired Anderson Howard Electric, Inc., to do the electrical installation work onsite. Anderson Howard Electric had locks on the breakers when they performed work on the equipment, and removed the locks when they finished their work onsite. W.E. O'Neil, the controlling contractor, did not ensure the breakers were locked out or tagged after Anderson Howard Electric left the project. Pfinish Koncepts dba Stone Craft employees, laying out the floor installation and using rollers attached to poles and sponges to apply sealant on the floor next to the receptacle boxes, were exposed to the hazard of contacting electricity.
Recent events (2)
- — I (S) $0
- — Z (S) $1785
More inspections at W.E. O'Neil Construction Company of California
View W.E. O'Neil Construction Company of California's full OSHA safety record →
More inspections in this industry (NAICS 236220)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340669258.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.