Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BAKER ELECTRIC, INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BAKER ELECTRIC, INC in KELSEY'S RENOVATION PROJECT AT THE PECHANGA RESORT & CASINO 45000 PECHANGA PARKWAY, TEMECULA, CA 92592 (NAICS 238210). OSHA activity number 340678713.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Baker Electric, INC — free Get an email when a new federal OSHA severe-injury report for Baker Electric, INC is published. One employer, no account, unsubscribe in one click.
Establishment
BAKER ELECTRIC, INC
Site address
KELSEY'S RENOVATION PROJECT AT THE PECHANGA RESORT & CASINO 45000 PECHANGA PARKWAY
City
TEMECULA
State
CA
ZIP
92592
Mailing
1298 PACIFIC OAKS PLACE, ESCONDIDO, CA 92029
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
251
Ownership type
A

1 citation on file for this inspection.

1926.417 B

Deleted Serious Gravity 1 1 instance 4 exposed
Issued
Jun 22, 2015
Abate by
Jun 30, 2015
Penalty
Initial $2,295 · Current $0 Reduced
29 CFR 1926.417(b): Equipment and circuits.  Equipment or circuits that were deenergized were not rendered inoperative and did not have tags attached at all points where such equipment or circuits can be energized:  At the project, the circuits that were deenergized were not rendered inoperative as the wires were not removed from the circuit breakers that controlled the circuits, and tags were not attached to each circuit breaker that could energize the circuits.  The circuits were located in rooms located adjacent to the project in panels FLK21 and FL2J.  Employees that demolished the bar area with pry bars, hammers, and other tools were exposed to the hazard of contacting electricity.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2295

View Baker Electric, INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340678713.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.