RADNOR, PA —
OSHA Inspection: BIOMED REALTY TRUST, INC.
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of BIOMED REALTY TRUST, INC. in 145 KING OF PRUSSIA ROAD, RADNOR, PA 19087 (NAICS 525930). OSHA activity number 340687748.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BIOMED REALTY TRUST, INC.
- Site address
- 145 KING OF PRUSSIA ROAD
- City
- RADNOR
- State
- PA
- ZIP
- 19087
- Mailing
- 101 MAIN STREET, 16TH FLOOR, CAMBRIDGE, MA 02142
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 525930
- Employees
- 10
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.416 A01
- Issued
- Oct 13, 2015
- Abate by
- Oct 19, 2015
- Penalty
- Initial $6,300 · Current $0 Reduced
General-duty citation text
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: a. Paralleling Switchgear, 145 King of Prussia Road, Radnor, PA 19087 - The employer did not de-energize switchgear or isolate it through the use of guarding for employees dismantling switchgear equipment. Two subcontractor employees working near an opened switchgear cabinet were exposed to an arc-flash explosion. One employee sustained first degree burns to his face and second degree burns around both his arms and hands. Noted On or about April 13, 2015
Recent events (2)
- — I (S) $0
- — Z (S) $6300
1926.417 B
- Issued
- Oct 13, 2015
- Abate by
- Oct 19, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.417(b): Equipment or circuits that were de-energized were not rendered inoperative: a. Switchgear, 145 King of Prussia Road, Radnor, PA 19087 - The employer did not verify that all sources of electrical energy were isolated and rendered inoperative before the performance of work by subcontractor employees. Two subcontractor employees were exposed to an arc-flash explosion. Noted On or about April 13, 2015