Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ELECTRICAL SERVICES UNLIMITED, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of ELECTRICAL SERVICES UNLIMITED, INC. in 250 PIEDMONT AVENUE NE, ATLANTA, GA 30308 (NAICS 238210). OSHA activity number 340691369.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Electrical Services Unlimited, INC. — free Get an email when a new federal OSHA severe-injury report for Electrical Services Unlimited, INC. is published. One employer, no account, unsubscribe in one click.
Site address
250 PIEDMONT AVENUE NE
City
ATLANTA
State
GA
ZIP
30308
Mailing
PO BOX 129, HIRAM, GA 30141
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
30
Ownership type
A

2 citations on file for this inspection.

1926.405 A01 I

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Jul 16, 2015
Abate by
Jul 28, 2015
Penalty
Initial $3,500 · Current $0 Reduced
29 CFR 1926.405(a)(1)(i): Metal raceways, cable armor, and other metal enclosures for conductors were not metallically joined together into a continuous electric conductor and so connected to all boxes, fittings, and cabinets as to provide effective elect  a.  Roof Top - The electrical metal cable armor and conductor enclosure was not continuous and joined together.  The electrical conductors joined together both permanent metal raceways with temporary rubber covered circuits which powered the motors on the swing stage scaffold.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3500

1926.405 A02 II B

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Jul 16, 2015
Abate by
Jul 28, 2015
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(2)(ii)(B): Temporary wiring branch circuit conductors were not run as multiconductor cord, cable assemblies, open conductors, nor in raceways:  a.  Roof Top - The temporary wiring branch circuit used for powering the swing stage scaffold was a mixture of both temporary cable and fixed metallic raceways, thereby exposing the employees on the swing stage scaffold to potential fall hazards from electrical cable failures.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Electrical Services Unlimited, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340691369.