OSHA Inspection: GREENWALL VENDING

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of GREENWALL VENDING in 664 HWY 142, POPLAR BLUFF, MO 63901 (NAICS 454210). OSHA activity number 340766542.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Greenwall Vending — free Get an email when a new federal OSHA severe-injury report for Greenwall Vending is published. One employer, no account, unsubscribe in one click.
Establishment
GREENWALL VENDING
Site address
664 HWY 142
City
POPLAR BLUFF
State
MO
ZIP
63901
Mailing
3633 MCLANE DR., POPLAR BLUFF, MO 63901
Inspection type
Complaint (B)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
454210
Employees
7
Ownership type
A

9 citations on file for this inspection.

1910.36 B01

Serious Gravity 1 1 instance 7 exposed
Issued
Jul 15, 2015
Abate by
Aug 31, 2015
Penalty
Initial $1,200 · Current $840 Reduced
29 CFR 1910.36(b)(1): At least two exit routes were not available in the workplace to permit prompt evacuation of employees and other building occupants during an emergency, except as allowed in paragraph (b)(3) of this section. The exit routes must be located as far away as practical from each other so that if one exit route is blocked by fire or smoke, employees can evacuate using the second exit route:  a. At the 664 Hwy 142 shop/warehouse, only one approved exit route was available at the time of the inspection (note: overhead doors are not approved exits and another door was locked, did not have an approved opening mechanism, and was blocked by merchandise.  (NFPA 101-2000 was reviewed to establish the violation.)  Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $840
  • — Z (S) $1200

1910.304 G05

Serious Gravity 5 1 instance 7 exposed
Issued
Jul 15, 2015
Penalty
Initial $1,600 · Current $1,120 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  a. A refrigerator was used with a missing ground pin; live voltage was measured on the appliance case.
Recent events (2)
  • — I (S) $1120
  • — Z (S) $1600

1910.305 B02 I

Serious Gravity 5 1 instance 7 exposed
Issued
Jul 15, 2015
Abate by
Aug 31, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  a. In the front warehouse section of the building, two outlet receptacles used for energizing equipment, were missing covers and one was damaged.  Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A03 III

Serious Gravity 5 1 instance 7 exposed
Issued
Jul 15, 2015
Abate by
Aug 31, 2015
Penalty
Initial $1,600 · Current $1,120 Reduced
29 CFR 1910.334(a)(3)(iii): Adapters which interrupt the continuity of the equipment grounding connection were used:  a. Examples existed, such as the use of an adapter ("cheater plug") to power several lighting fixtures with an equipment grounding conductor (with a "ground pin") into a two wire extension cord.   Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $1120
  • — Z (S) $1600

1910.334 A03 I

Serious Gravity 5 1 instance 7 exposed
Issued
Jul 15, 2015
Abate by
Aug 31, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(3)(i): A flexible cord used with grounding type equipment did not contain an equipment grounding conductor:  a. Two wire extension cords were used to power equipment with three wire power cords, such as lighting fixtures.  Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 7 exposed
Issued
Jul 15, 2015
Abate by
Aug 31, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a. Extension cords were use to power equipment such as freezers, refrigerators, and permanent lighting.  Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 5 1 instance 7 exposed
Issued
Jul 15, 2015
Abate by
Aug 31, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:  a. Extension and power cords were run through walls, such as the extension cord to a refrigerator and a cooling fan plugged into an extension cord run through a wall hole.  Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 7 exposed
Issued
Jul 15, 2015
Abate by
Aug 31, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a. A power strip was used to power industrial equipment (freezers and refrigerator) and was not directly plugged into the permanent wiring of the building, but instead was plugged into an extension cord which was plugged into a "three way adapter," in violation of the listed use of the equipment.  Both electrical shock and fire hazards existed.  Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.242 A

Other-than-serious 1 instance 2 exposed
Issued
Jul 15, 2015
Abate by
Aug 31, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.242(a): Hand and portable powered tools or equipment were not kept in safe condition:  a. A pallet jack used to move equipment, such as vending machines, did not hold the load; hydraulic pressure was lost (note: 1910.244(a)(1)(ii) requires the intended load to be legible on the jack; and 1910.244(a)(1)(viii) requires that equipment in disrepair be tagged out and not used until in working order).   Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).