Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CLINTON'S DITCH COOPERATIVE CO., INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CLINTON'S DITCH COOPERATIVE CO., INC. in 8478 PARDEE ROAD, CICERO, NY 13039 (NAICS 312111). OSHA activity number 340773035.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Clinton'S Ditch Cooperative CO., INC. — free Get an email when a new federal OSHA severe-injury report for Clinton'S Ditch Cooperative CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
8478 PARDEE ROAD
City
CICERO
State
NY
ZIP
13039
Mailing
8478 PARDEE ROAD, CICERO, NY 13039
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
312111
Employees
170
Ownership type
A

7 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 32 exposed
Issued
Oct 13, 2015
Abate by
May 1, 2016
Penalty
Initial $4,500 · Current $3,150 Reduced
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were potentially exposed to chemical burns and inhalation hazards from an uncontrolled release of anhydrous ammonia.       a) Throughout the ammonia system, on or about 7/14/2015: The employer did not take measures to limit potential for corrosion of pipes and equipment which handled anhydrous ammonia and also had no inspection and/or testing procedures to evaluate the mechanical integrity of pipes and equipment which handled anhydrous ammonia. Damaged insulation and vapor barriers as well as corroded pipes and were visible throughout the system.      b) On the ammonia system, on or about 7/14/2015: The employer did not perform inspections, tests, or replace pressure relief valves on a scheduled basis to ensure that pressure relief valves were maintained in good working order.      Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $3150
  • — Z (S) $4500

1910.95 G08 II B

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 13, 2015
Abate by
Nov 15, 2015
Penalty
Initial $5,400 · Current $1,890 Reduced
29 CFR 1910.95(g)(8)(ii)(B): Unless a physician determines that the standard threshold shift is not work-related or aggravated by occupational noise exposure, the employer did not ensure, when a standard threshold shift occurs, that for employees already using hearing protectors, employees be refitted and retrained in the use of hearing protectors and provided with hearing protectors offering greater attenuation if necessary:      a) At the facility, on or about 8/27/15: Where employees audiogram results showed a standard threshold shift had occurred, the employer did not ensure that employees were refitted and retrained in the use of hearing protection and provided with hearing protectors offering greater attenuation if necessary.        Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $1890
  • — Z (S) $5400

1910.120 Q02

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 13, 2015
Abate by
Nov 15, 2015
Penalty
Initial $4,500 · Current $3,150 Reduced
29 CFR 1910.120(q)(2): The employer did not develop an emergency response plan for emergencies which addressed the following minimum requirements of this standard: 1910.120(q)(2)(i) through 1910.120(q)(2)(xii):          a) At the facility, on or about 7/14/15: The employer did not develop an emergency response plan for employees authorized to investigate or respond to a release of anhydrous ammonia.         Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $3150
  • — Z (S) $4500

1910.120 Q06 II

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 13, 2015
Abate by
Nov 15, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.120(q)(6)(ii): First responders at the operational level did not receive at least eight hours of training or did not have sufficient experience to objectively demonstrate competency in the areas required by 29 CFR 1910.120(q)(6)(ii)(A) through (q)(6)(ii)(F) and/or the employer did not so certify:     a) At the facility, on or about 7/14/15: Employees who were authorized to investigate releases of ammonia and attempt to mitigate a release in a defensive manner were not able to demonstrate competency in risk assessment and the limits of their personal protective equipment.    Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 D03 III B 2

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 13, 2015
Abate by
Nov 15, 2015
Penalty
Initial $2,700 · Current $1,890 Reduced
29 CFR 1910.134(d)(3)(iii)(B)(2): The employer did not implement a change schedule for respirators not equipped with an End of Service Life Indicator that would ensure cartridges were changed before the end of their service life:        a) At the facility, on or about 7/21/15: Employees wore negative pressure full face respirators with ammonia cartridges when investigating/responding to releases of ammonia. A change schedule had not been implemented for respirator cartridges.         Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $1890
  • — Z (S) $2700

1910.134 F02

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 13, 2015
Abate by
Nov 15, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.134(f)(2): Employee(s) using a tight-fitting facepiece respirator were not annually fit tested:      a) At the facility, on or about 7/21/15: Employees who wore full face negative pressure respirators had not been fit tested within the past year.      Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1904.10 A

Other-than-serious 1 instance 3 exposed
Issued
Oct 13, 2015
Abate by
Nov 15, 2015
Penalty
Initial $0 · Current $0
29 CFR 1904.10(a): Where an employee's hearing test (audiogram) revealed that the employee had experienced a work-related Standard Threshold Shift (STS) in hearing in one or both ears, and the employee's total hearing level was 25 decibels (dB) or more above audiometric zero (averaged at 2000, 3000, and 4000 Hz) in the same ear(s) as the STS, the employer did not record the case on the OSHA 300 Log.   a) At the facility, on or about 4/22/15: 3 cases where an employees audiogram showed an STS were not recorded on the 2015 OSHA 300 injury and illness log.      Abatement certification must be submitted for this item.