On , OSHA opened a planned safety inspection of MID FLORIDA FREEZER WAREHOUSES, LTD in 2560 WEST HWY 441, APOPKA, FL 32712 (NAICS 493120). OSHA activity number 340792134.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch MID Florida Freezer Warehouses, LTD — free Get an email when a new federal OSHA severe-injury report for MID Florida Freezer Warehouses, LTD is published. One employer, no account, unsubscribe in one click.
Site address
2560 WEST HWY 441
City
APOPKA
State
FL
ZIP
32712
Mailing
2560 WEST HWY 441, APOPKA, FL 32712
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
20
Ownership type
A

5 citations on file for this inspection.

1910.134 C01

Serious Gravity 5 1 instance 3 exposed
Issued
Dec 11, 2015
Abate by
Feb 1, 2016
Penalty
Initial $2,000 · Current $1,000 Reduced
29 CFR 1910.134(c)(1): A written respiratory protection program that included the provisions in 29 CFR 1910.134(c)(1)(i) - (ix) with worksite specific procedures was not established and implemented for required respirator use:   (a) At the establishment located on 2560 W. Hwy 441, Apopka, FL, employees engaged in the operation of the ammonia refrigeration system were provided and required the use of Survivair, full face, with dual ammonia cartridges, respirators, when handling events of "minor" ammonia discharge. No written policy program had been established, on or about, 07/21/2015.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1910.134 E01

Serious Gravity 5 1 instance 3 exposed
Issued
Dec 11, 2015
Abate by
Feb 1, 2016
Penalty
Initial $2,000 · Current $1,000 Reduced
29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace:   (a) At the establishment located on 2560 W. Hwy 441, Apopka, FL, employees engaged in the operation of the ammonia refrigeration system were provided and required the use of Survivair, full face, with dual ammonia cartridges, respirators, when handling events of "minor" ammonia discharge. No evaluation had been provided, on or about, 07/21/2015.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1910.134 F01

Serious Gravity 5 1 instance 3 exposed
Issued
Dec 11, 2015
Abate by
Feb 1, 2016
Penalty
Initial $2,000 · Current $1,000 Reduced
29 CFR 1910.134(f)(1): The employer did not ensure that employee(s) required to use a tight-fitting facepiece respirator passed the appropriate qualitative fit test (QLFT) or quantitative fit test (QNFT):    (a) At the establishment located on 2560 W. Hwy 441, Apopka, FL, employees engaged in the operation of the ammonia refrigeration system were provided and required the use of Survivair, full face, with dual ammonia cartridges, respirators, when handling events of "minor" ammonia discharge. No fit testing had been provided, on or about, 07/21/2015.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1910.134 K

Serious Gravity 5 1 instance 3 exposed
Issued
Dec 11, 2015
Abate by
Feb 1, 2016
Penalty
Initial $2,000 · Current $1,000 Reduced
29 CFR 1910.134(k): The employer did not provide comprehensive, understandable training which did not occur annually and/or more often if necessary:  (a) At the establishment located on 2560 W. Hwy 441, Apopka, FL, employees engaged in the operation of the ammonia refrigeration system were provided and required the use of Survivair, full face, with dual ammonia cartridges, respirators, when handling events of "minor" ammonia discharge. No annual training on the use and limitations had been provided, on or about, 07/21/2015.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1910.119 D03 I B

Other-than-serious 1 instance 3 exposed
Issued
Dec 11, 2015
Abate by
Jun 30, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.119(d)(3)(i)(B): The employer did not include all equipment that was part of the process on piping and instrument diagrams;  (a) At the establishment located on 2560 W. Hwy. 441, Apopka, FL, the piping and instrumentation diagram (P&ID's) information of the ammonia refrigeration system was not kept up to date to include the changes to the system that included, but not limited to, the installation of Aircoil evaporators, on or about, 02/19/2013. No updated P&ID's were available, on or about, 07/21/2015.