Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: STONERIDGE

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of STONERIDGE in 300 DAN ROAD, CANTON, MA 02021 (NAICS 335999). OSHA activity number 340794841.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Stoneridge — free Get an email when a new federal OSHA severe-injury report for Stoneridge is published. One employer, no account, unsubscribe in one click.
Establishment
STONERIDGE
Site address
300 DAN ROAD
City
CANTON
State
MA
ZIP
02021
Mailing
300 DAN ROAD, CANTON, MA 02021
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
335999
Employees
300
Ownership type
A

4 citations on file for this inspection.

1910.332 B01

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 23, 2015
Abate by
Dec 31, 2015
Penalty
Initial $7,000 · Current $5,500 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    The company had not trained the Plant Electrician or his helper in safe electrical work practices.
Recent events (2)
  • — I (S) $5500
  • — Z (S) $7000

1910.335 A01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 23, 2015
Abate by
Dec 31, 2015
Penalty
Initial $7,000 · Current $5,500 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    Location:  Main Electrical Room    Employees did not use appropriate personal protective equipment ( PPE ) while performing electrical work which exposed them to an arc flash hazard.  An arc flash occurred and caused burns to the employees arms.
Recent events (2)
  • — I (S) $5500
  • — Z (S) $7000

1910.333 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 23, 2015
Abate by
Dec 31, 2015
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:    Jobsite:  Main Electrical Room    An employee worked on an energized switch board and, as a result, suffered an arc flash injury.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

1910.303 B02

Other-than-serious 2 instances 2 exposed
Issued
Oct 23, 2015
Abate by
Nov 2, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Location:  Main Electrical Room  Electrical tape was used to cover blank openings in Switch Boards.  Instance A:  Cutler-Hammer 480 / 277 volt switch board  Instance B:   Cutler-Hammer 208 volt switch board
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340794841.