BRONX, NY —
OSHA Inspection: KJK ELECTRIC INC.
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of KJK ELECTRIC INC. in 2477 3RD AVE., BRONX, NY 10451 (NAICS 238210). OSHA activity number 340818889.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KJK ELECTRIC INC.
- Site address
- 2477 3RD AVE.
- City
- BRONX
- State
- NY
- ZIP
- 10451
- Mailing
- 33-18 FARRINGTON ST., FLUSHING, NY 11354
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 8
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.403 H
- Issued
- Sep 4, 2015
- Penalty
- Initial $1,200 · Current $720 Reduced
General-duty citation text
29 CFR 1926.403(h): Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident: On or about 6/29/15 Location: 2477 3rd Ave. Bronx NY, 10451 a) The 208 volt temporary power circuit breaker panel did not have individual breakers labled to indicate their purpose.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1926.405 A02 II F
- Issued
- Sep 4, 2015
- Abate by
- Oct 1, 2015
- Penalty
- Initial $2,000 · Current $1,200 Reduced
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(F): Temporary lights were suspended by their electric cords when such lights and cords were not designed for suspension: On or about: 6/29/15 Location: 2744 3rd Ave. Bronx NY a) Temporary lighting was suspended by its electrical cord while hanging over structural steel and metal framing.
Recent events (2)
- — I (S) $1200
- — Z (S) $2000
1926.405 B01
- Issued
- Sep 4, 2015
- Penalty
- Initial $2,000 · Current $1,200 Reduced
General-duty citation text
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed: On or about: 6/29/15 Location: 2477 3rd Ave. Bronx NY a) Numerous breaker openings in the 208 volt temporary power circuit breaker panel were open.
Recent events (2)
- — I (S) $1200
- — Z (S) $2000
1926.405 E02
- Issued
- Sep 4, 2015
- Abate by
- Sep 17, 2015
- Penalty
- Initial $2,000 · Current $1,200 Reduced
General-duty citation text
29 CFR 1926.405(e)(2): Switches, circuit breakers, and switchboards installed in wet locations were not enclosed in weatherproof enclosures: On or about: 6/29/15 Location: 2477 3rd Ave. Bronx NY a) The 208 volt temporary power circuit breaker panel located was exposed to rain, snow, and other elements. The circuit breaker panel did not have an adequate roof or canopy protecting it.
Recent events (2)
- — I (S) $1200
- — Z (S) $2000
More inspections at KJK Electric INC.
View KJK Electric INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340818889.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.