PRUDHOE BAY, AK —
OSHA Inspection: HILCORP ALASKA, LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of HILCORP ALASKA, LLC in ENDICOTT ISLAND MPI, PRUDHOE BAY, AK 99734 (NAICS 211111). OSHA activity number 340819622.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HILCORP ALASKA, LLC
- Site address
- ENDICOTT ISLAND MPI
- City
- PRUDHOE BAY
- State
- AK
- ZIP
- 99734
- Mailing
- PO BOX 340067, PRUDHOE BAY, AK 99734
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 211111
- Employees
- 76
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.219 D01
- Issued
- Aug 25, 2015
- Penalty
- Initial $2,168 · Current $1,084 Reduced
General-duty citation text
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o): Endicott MPI, Sewage Treatment Plant: On or about 28 July 2015 and times prior thereto, two Effluent sewage pump pulleys had an opening measuring approximately 8 inches by 8 inches. This condition exposed employees to a caught in hazard.
Recent events (2)
- — I (S) $1084
- — Z (S) $2168
1910.303 F02
- Issued
- Aug 25, 2015
- Abate by
- Sep 16, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident. Endicott Island, MOC, Carpenter Room: On or about 28 July 2015 and times prior thereto, electrical panel PAP-E3-4539 was not properly identified with a listing for the circuits. This condition exposed employees to an electrical shock and burn hazard.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G01 IV A
- Issued
- Aug 25, 2015
- Abate by
- Sep 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure Endicott MPI, Water Plant: On or about 28 July 2015 and times prior thereto, a 50 foot polar/Solar 12-3 extension cord was routed and connected to stanchion to operate the corrosion inhibitor pump. This condition exposed employees to an electrical shock and burn hazard.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Hilcorp Alaska, LLC
View Hilcorp Alaska, LLC's full OSHA safety record →
More inspections in this industry (NAICS 211111)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340819622.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.