OSHA Inspection: WEISINGER ELECTRIC INC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of WEISINGER ELECTRIC INC in 300 WINSTON STREET, LUFKIN, TX 75901 (NAICS 238210). OSHA activity number 340831825.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Weisinger Electric INC — free Get an email when a new federal OSHA severe-injury report for Weisinger Electric INC is published. One employer, no account, unsubscribe in one click.
Site address
300 WINSTON STREET
City
LUFKIN
State
TX
ZIP
75901
Mailing
404 E FRANK, LUFKIN, TX 75901
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
18
Ownership type
A

3 citations on file for this inspection.

1910.269 D02 IV B

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 27, 2015
Abate by
Nov 16, 2015
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.269(d)(2)(iv)(B): The employer did not provide specific procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy.   On or about July 31, 2015, at the job site near Gate 13,  where employees were exposed to electrical hazards when changing out a transformer without being provided specific procedural steps for shutting down, isolating, blocking and securing equipment to control hazardous energy.
Recent events (1)
  • — Z (S) $2800

1910.269 D02 IV D

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 27, 2015
Abate by
Nov 16, 2015
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.269(d)(2)(iv)(D): The employer did not provided specific requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control measures.  This violation occurred on or about July 31, 2015 at the job site near Gate 13, where an employee was was exposed to electrical hazards when the employer did not provided specific requirements for testing the power line to determine and verify the effectiveness of lockout devices and other energy control measures.
Recent events (1)
  • — Z (S) $2800

1910.269 M03 II

Serious Gravity 10 1 instance 1 exposed
Issued
Oct 27, 2015
Abate by
Nov 16, 2015
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.269(m)(3)(ii): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment were deenergized or open.   On or about July, 31, 2015, at GE Facility, an employee was exposed to electrical hazards when one phase of the feeder wires was attached to the power line that was not deenergized or open.