On , OSHA opened a planned safety inspection of CAPITOL MANUFACTURING in 1125 CAPITOL ROAD, CROWLEY, LA 70526 (NAICS 332919). OSHA activity number 340848795.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CAPITOL MANUFACTURING
- Site address
- 1125 CAPITOL ROAD
- City
- CROWLEY
- State
- LA
- ZIP
- 70526
- Mailing
- 1125 CAPITOL AVE., CROWLEY, LA 70526
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332919
- Employees
- 207
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.147 C02 II
- Issued
- Oct 1, 2015
- Abate by
- Oct 7, 2015
- Penalty
- Initial $6,000 · Current $3,600 Reduced
General-duty citation text
29 CFR 1910.147(c)(2)(ii): If an energy isolating device is capable of being locked out, the employer's energy control program under paragraph (c)(1) of this section did not utilize lockout, and the employer did not demonstrate that the utilization of a tagout system provided full employee protection as set forth in paragraph (c)(3) of this section. On or about July 22, 2015, in Department 10 Conomatics, Department 5 Nipple, Department 11 Goss, Department 3 Threaders, and Department 18 CNC, the employer allowed employees covered under the Lockout-Tagout standard to utilize tagout procedures for the control of hazardous energy on a wide assortment of BTB, Nipple Shop Hand and Auto Stamper,Wheelabrator, electrical circuit breakers and Warehouse Stockman/Komatsu machines when the machines were capable of being locked out.
Recent events (2)
- · I (S) $3600
- · Z (S) $6000
1910.303 G02 I
- Issued
- Oct 1, 2015
- Abate by
- Oct 7, 2015
- Penalty
- Initial $7,000 · Current $4,200 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures. On or about July 22, 2015, in the Maintenance Machine shop; the employer allowed employees to be exposed to live parts (three missing breakers) in the 220 Single Phase General Electrical panel box that controls the lights, thus exposing employees to serious electrical injuries.
Recent events (2)
- · I (S) $4200
- · Z (S) $7000
1910.22 D01
- Issued
- Oct 1, 2015
- Abate by
- Oct 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(d)(1): In every building or other structure, or part thereof, used for mercantile, business, industrial, or storage purposes, the loads approved by the building official were not marked on plates of approved design which were not supplied and securely affixed by the owner of the building, or his duly authorized agent, in a conspicuous place in each space to which they relate: On or about July 22, 2015, above the Engineer's office in buildings #3 and #2 used for storage, the employer allowed employees to work in the spaces below the storage areas without load limit markings indicating load limits.
Recent events (2)
- · I (O) $0
- · Z (O) $0
1910.303 F02
- Issued
- Oct 1, 2015
- Abate by
- Oct 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about July 22, 2015, in the Maintenance shop; the employer allowed employees to connect and disconnect breakers in two unlabeled auxiliary and one main power electrical power boxes for the welding machine and two grinders.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections at Capitol Manufacturing
View Capitol Manufacturing's full OSHA safety record →
More inspections in this industry (NAICS 332919)
More inspections in LA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 340848795.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.