WADSWORTH, OH —
OSHA Inspection: BURNS AND MCDONNELL ENGINEERING COMPANY, INC.
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of BURNS AND MCDONNELL ENGINEERING COMPANY, INC. in 9681 SILVER CREEK ROAD, WADSWORTH, OH 44281 (NAICS 541330). OSHA activity number 340850254.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BURNS AND MCDONNELL ENGINEERING COMPANY, INC.
- Site address
- 9681 SILVER CREEK ROAD
- City
- WADSWORTH
- State
- OH
- ZIP
- 44281
- Mailing
- 9400 WARD PARKWAY, KANSAS CITY, MO 64114
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 541330
- Employees
- 5400
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.950 C02 II
- Issued
- Oct 9, 2015
- Penalty
- Initial $6,300 · Current $0 Reduced
General-duty citation text
29 CFR 1926.950(c)(2)(ii): Before work begins, the contract employer shall advise the host employer of any unique hazardous conditions presented by the contract employer''s work. On or about July 30, 2015, before conducting a power factor test during the installation of a transformer the employer, working as the contractor employer, failed to ensure the host employers employees were advised of the unique hazardous conditions of performing a 10kV power factor test of the transformer.
Recent events (3)
- — F (S) $0
- — C (S) $6300
- — Z (S) $6300
1926.950 C03
- Issued
- Oct 9, 2015
- Abate by
- Nov 5, 2015
- Penalty
- Initial $6,300 · Current $6,300
General-duty citation text
29 CFR 1926.950(c)(3): Joint host- and contract-employer responsibilities. The contract employer and the host employer shall coordinate their work rules and procedures so that each employee of the contract employer and the host employer is protected as required by this subpart. On or about July 30, 2015, during the installation of a substation transformer the employer, operating as the contract employer, failed to coordinate their work rules and procedures with the host employer for protecting test areas where host employer and contract employer employees were working jointly.
Recent events (3)
- — F (O) $6300
- — C (S) $6300
- — Z (S) $6300
1926.963 B01
- Issued
- Oct 9, 2015
- Penalty
- Initial $6,300 · Current $0 Reduced
General-duty citation text
29 CFR 1926.963(b)(1): Safe work practices. The employer shall establish and enforce work practices for the protection of each worker from the hazards of high-voltage or high-power testing at all test areas, temporary and permanent. Such work practices shall include, as a minimum, test area safeguarding, grounding, the safe use of measuring and control circuits, and a means providing for periodic safety checks of field test areas. On or about July 30, 2015, during a transformer installation project, the employer failed to enforce test area safe work practices for the protection of workers from the hazards of 10kV power factor test conducted on the substation transformer.
Recent events (3)
- — F (S) $0
- — C (S) $6300
- — Z (S) $6300
1926.963 B02
- Issued
- Oct 9, 2015
- Abate by
- Nov 5, 2015
- Penalty
- Initial $6,300 · Current $0 Reduced
General-duty citation text
29 CFR 1926.963(b)(2): Training. The employer shall ensure that each employee, upon initial assignment to the test area, receives training in safe work practices, with retraining provided as required by � 1926.950(b). On or about July 30, 2015, during a transformer installation project, the employer failed to ensure an employee was trained in the safe work practices of conducting a power factor test on a substation transformer.
Recent events (3)
- — F (S) $0
- — C (S) $6300
- — Z (S) $6300
More inspections at Burns and Mcdonnell Engineering Company, INC.
View Burns and Mcdonnell Engineering Company, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 541330)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340850254.