Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ALABAMA POWER COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ALABAMA POWER COMPANY in 1905 OLD HIGHWAY 411 AND BRENTWOOD AVENUE, GADSDEN, AL 35901 (NAICS 221122). OSHA activity number 340855774.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Alabama Power Company — free Get an email when a new federal OSHA severe-injury report for Alabama Power Company is published. One employer, no account, unsubscribe in one click.
Site address
1905 OLD HIGHWAY 411 AND BRENTWOOD AVENUE
City
GADSDEN
State
AL
ZIP
35901
Mailing
600 NORTH 18TH STREET, BIRMINGHAM, AL 35203
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
120
Ownership type
A

2 citations on file for this inspection.

1910.269 L03 I

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Nov 18, 2015
Abate by
Dec 1, 2015
Penalty
Initial $4,250 · Current $0 Reduced
29 CFR 1910.269(l)(3)(i): The employer did not establish minimum approach distances no less than the distances computed by Table R-3 for ac systems or Table R-8 for dc systems:  (a) On or about 8/12/2015 - 1905 Old Highway 411 and Brentwood Avenue, Gadsden, AL, 35203, the employer did not determine the minimum approach distance for an employee replacing a 3 phase set of switches on a 7,200-volt electrical pole.
Recent events (3)
  • — J (S) $0
  • — C (S) $4250
  • — Z (S) $4250

1910.269 L04 I

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Nov 18, 2015
Abate by
Dec 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.269(l)(4)(i): When an employee uses rubber insulating gloves as insulation from energized parts (under paragraph (l)(3)(iii)(A) of this section), the employer did not ensure that the employee also used rubber insulating sleeves:  (a) On or about 8/12/2015 - 1905 Old Highway 411 and Brentwood Avenue, Gadsden, AL, an employee replacing a 3 phase set of switches on a 7,200-volt electrical pole was not wearing rubber insulating sleeves.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

View Alabama Power Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340855774.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.