CORINTH, NY —
OSHA Inspection: EQUITY LIFESTYLE PROPERTIES, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of EQUITY LIFESTYLE PROPERTIES, INC. in 78 HEATH ROAD, CORINTH, NY 12822 (NAICS 721211). OSHA activity number 340871854.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EQUITY LIFESTYLE PROPERTIES, INC.
- Site address
- 78 HEATH ROAD
- City
- CORINTH
- State
- NY
- ZIP
- 12822
- Mailing
- 78 HEATH ROAD, CORINTH, NY 12822
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721211
- Employees
- 1600
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.303 B07 IV
- Issued
- Feb 18, 2016
- Abate by
- Jun 21, 2017
- Penalty
- Initial $7,000 · Current $12,675
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of electric equipment, such as parts that were broken, bent, cut or deteriorated by corrosion, chemical action, or overheating: a) Campsite - On or about August 25, 2015, 120 Volt, 30 amp breaker field boxes throughout the campsite, including, but not limited to, PANEL 300 A field box, were exposed to the elements such as, but not limited to, rain, snow, wind, etc. Parts were damaged and rusted with openings allowing the elements to enter the box and cause damage exposing employees to electrical hazards.
Recent events (3)
- — F (S) $12675
- — C (S) $7000
- — Z (S) $7000
1910.303 F02
- Issued
- Feb 18, 2016
- Abate by
- Jun 21, 2017
- Penalty
- Initial $7,000 · Current $12,675
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Campsite- On or about August 25, 2015 and December 4, 2015, 120 Volt, 30 amp breaker field boxes throughout the campsite were not adequately labeled. The breakers in the field boxes were not labeled to indicate the correct and corresponding campsite box. The breakers in the field boxes must be properly labeled to ensure employees can turn off the power to the correct and corresponding campsite box to safely perform any servicing or maintenance operations on that campsite box, and avoid electrical hazards.
Recent events (3)
- — F (S) $12675
- — C (S) $7000
- — Z (S) $7000
1910.303 F03
- Issued
- Feb 18, 2016
- Abate by
- Jun 21, 2017
- Penalty
- Initial $5,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(f)(3): The markings required by paragraphs (f)(1) and (f)(2) of 29 CFR 1910.303 were not sufficiently durable to withstand the environment involved: a) Campsite - On or about August 25, 2015 and December 4, 2015, breakers in the 120 Volt, 30 amp field boxes throughout the campsite, including, but not limited to, the PANEL 300 A field box, had markings that were labeled with sharpie marker, and were starting to fade and rub off, which shows these markings were not sufficiently durable to withstand the environment involved, exposing employees to electrical hazards from operating improperly identified circuit breakers.
Recent events (3)
- — F (S) $0
- — C (S) $5000
- — Z (S) $5000
1910.305 B01 II
- Issued
- Feb 18, 2016
- Abate by
- Jun 22, 2017
- Penalty
- Initial $7,000 · Current $12,675
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Campsite - On or about August 25, 2015 and December 4, 2015, there were unused openings that were not closed throughout the campsite in the 120 Volt, 30 amp breakers field boxes, including but not limited to, the PANEL 300 A field box which exposed employees to electrical hazards.
Recent events (3)
- — F (S) $12675
- — C (S) $7000
- — Z (S) $7000
1910.332 B01
- Issued
- Feb 18, 2016
- Abate by
- Jun 22, 2017
- Penalty
- Initial $7,000 · Current $12,675
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a) Worksite - On or prior to August 25, 2015, employees were not trained in safety-related work practices, including but not limited to, how to safely test and operate electrical equipment, use and selection of personal protective equipment (PPE), how to deenergize electrical equipment, when to deenergize electrical equipment, lockout/tagout of electrical equipment, the hazards of arc-flash, and general electrical hazards that pertain to their work when exposed to energized parts. Employees were required to operate, text, troubleshoot, replace and maintain electrical equipment at the facility.
Recent events (3)
- — F (S) $12675
- — C (S) $7000
- — Z (S) $7000
1910.334 B02
- Issued
- Feb 18, 2016
- Abate by
- Jun 22, 2017
- Penalty
- Initial $7,000 · Current $12,675
General-duty citation text
29 CFR 1910.334(b)(2): After a circuit protective device operates to deenergize the circuit, the circuit was manually reenergized repetitively without determining that the automatic operation of the device was caused by an overload rather than a fault, and that the equipment and circuit could be safely energized. The repetitive manual reclosing of circuit breakers was not prohibited: a) Campsite - On or prior to August 22, 2015, employees were exposed to electrical hazards due to the repetitive manual reclosing of tripped circuit breakers without determining why the breakers tripped.
Recent events (3)
- — F (S) $12675
- — C (S) $7000
- — Z (S) $7000
1910.335 A01 I
- Issued
- Feb 18, 2016
- Abate by
- Jun 22, 2017
- Penalty
- Initial $7,000 · Current $12,675
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with and did not use electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: a) Worksite - On or prior to August 25, 2015, employees required to operate, test, troubleshoot, replace and maintain electrical equipment at the facility were not provided with and did not use electrical protective equipment, such as insulated gloves and face shield, appropriate for the specific parts of the body that need to be protected and for the work being performed.
Recent events (3)
- — F (S) $12675
- — C (S) $7000
- — Z (S) $7000
1910.303 B02
- Issued
- Feb 18, 2016
- Abate by
- Jun 22, 2017
- Penalty
- Initial $70,000 · Current $12,675 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Campsite - On or prior to August 25, 2015, the employer did not provide adequate electric service to, and did not regard the manufacturer's labeling placed on the boxes' inside covers, on the campsite boxes. The campsite boxes are manufactured by Milbank, Model #U5000 Series, and are NEMA 3R (rainproof) rated. Each campsite box contained one 50 amp double-pole circuit, one 30-amp, single-pole circuit, and one 20 amp/120 volt duplex receptacle circuit, that were all supplied by one single-pole 30-amp breaker in the field boxes installed ahead of the campsite boxes. The campsite box can draw a maximum of 100 amps of service that is only being supplied by one single-pole 30-amp breaker at the field box, therefore causing the single-pole 30-amp breaker at the field box to be overloaded, which then results in the repetitive tripping of this single-pole 30-amp breaker at the field box. The undersized and inappropriately wired service exposed employees to potential hazards of arc flash from the constant resetting of circuit breaker until it faults. b) Campsite - On or about August 25, 2015 and December 4, 2015, covers were not properly fixed and secured to the field boxes creating unused openings, exposing live parts, throughout the campsite in the 120 Volt, 30 amp breakers field boxes, including but not limited to, the Panel 300 A field box which exposed employees to electrical hazards.
Recent events (3)
- — F (W) $12675
- — C (W) $70000
- — Z (W) $70000
1910.333 A
- Issued
- Feb 18, 2016
- Abate by
- Jun 22, 2017
- Penalty
- Initial $70,000 · Current $12,675 Reduced
General-duty citation text
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized: a) Campsite - On or prior to August 22, 2015, safety related work practices, including but not limited to, de-energizing and locking out electrical equipment, using appropriate electrical protective equipment and using appropriate personal protective equipment were not employed to protect workers required to operate, test, troubleshoot, replace and maintain electrical equipment at the facility. b) Campsite - On or about August 25, 2015 and December 4, 2015, covers were not properly fixed and secured to the field boxes creating openings and exposing live parts, throughout the campsite in the 120 Volt, 30 amp breakers field boxes, including but not limited to, the Panel 300 A field box which exposed employees to electrical hazards.
Recent events (3)
- — F (W) $12675
- — C (W) $70000
- — Z (W) $70000
More inspections at Equity Lifestyle Properties, INC.
View Equity Lifestyle Properties, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 721211)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340871854.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.