Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CRC INDUSTRIES, INCORPORATED

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CRC INDUSTRIES, INCORPORATED in 885 LOUIS DRIVE, WARMINSTER, PA 18974 (NAICS 325998). OSHA activity number 340886977.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch CRC Industries, Incorporated — free Get an email when a new federal OSHA severe-injury report for CRC Industries, Incorporated is published. One employer, no account, unsubscribe in one click.
Site address
885 LOUIS DRIVE
City
WARMINSTER
State
PA
ZIP
18974
Mailing
885 LOUIS DRIVE, WARMINSTER, PA 18974
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325998
Employees
140
Ownership type
A

5 citations on file for this inspection.

1910.119 E01

Serious Gravity 5 1 instance 20 exposed
Issued
Jan 8, 2016
Abate by
May 2, 2016
Penalty
Initial $3,825 · Current $3,400 Reduced
29 CFR 1910.119(e)(1): The employer did not perform an initial process hazard analysis (hazard evaluation) on processes covered by 29 CFR 1910.119:    a) Mixing rooms 1 and 2 and connected product filling lines - On or about August 31, 2015, the employer operated a Process Safety Management (PSM) covered mixing and filling process with a capacity of greater than 10,000 lbs. of flammable liquid, as defined in 1910.119(a)(1)(ii), without a Process Hazard Analysis (PHA) completed for the process that included these operations.
Recent events (2)
  • — I (S) $3400
  • — Z (S) $3825

1910.119 L01

Serious Gravity 5 2 instances 20 exposed
Issued
Jan 8, 2016
Abate by
Jan 18, 2016
Penalty
Initial $3,825 · Current $3,300 Reduced
29 CFR 1910.119(l)(1): The employer did not implement procedures to manage changes to process chemicals, technology, equipment, and procedures, and changes to facilities that affect a covered process:     a) Tank farm, Propellant Storage Tanks - On or about August 31, 2015, the employer had not implemented management of change procedures for the installation of the air actuated emergency shut-off valves installed on the Propellant Storage Tanks in 2011.    b) Steam/Water heat exchanger - On or about August 31, 2015, the employer had not implemented management of change procedures for the installation of the PSV to the Steam/Water heat exchanger that occurred in 2012.
Recent events (2)
  • — I (S) $3300
  • — Z (S) $3825

1910.119 E03 VII

Serious Gravity 5 1 instance 20 exposed
Issued
Jan 8, 2016
Penalty
Initial $3,060 · Current $3,300
29 CFR 1910.119(e)(3)(vii): The process hazard analysis did not address a qualitative evaluation of a range of the possible safety and health effects of failure of controls on employees in the workplace.    a) PHA revalidation - On or about August 31, 2015, a majority of actions recommended by the employer's revalidation had not been adequately addressed by a qualitative evaluation to assess severity and probability. Of 10 recommendations, eight items were given no risk level rating.
Recent events (2)
  • — I (S) $3300
  • — Z (S) $3060

1910.119 F01 III B

Serious Gravity 5 1 instance 10 exposed
Issued
Jan 8, 2016
Abate by
Jan 18, 2016
Penalty
Initial $3,060 · Current $0 Reduced
29 CFR 1910.119(f)(1)(iii)(B):  The employer's Standard Operating Procedures did not include precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment;    a) Aerosol lines 1 and 2 - On or about August 31, 2015, The employer had not developed Standard Operating Procedures for changing product filters at the aerosol filling stations, as recommended by the PHA revalidation study.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3060

1910.119 E05

Other-than-serious 1 instance 20 exposed
Issued
Jan 8, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.119(e)(5): The employer did not complete actions to resolve PHA recommendations as soon as possible:    a) PSM covered propellant system - On or about August 31, 2015 the employers projected dates for resolution of PHA recommendations were all set at 1 year, proposed actions were not documented, and no personnel were assigned to complete the recommendations.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

View CRC Industries, Incorporated's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340886977.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.