BRONX, NY ·
OSHA Inspection: MAR-SAL PLUMBING & HEATING, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of MAR-SAL PLUMBING & HEATING, INC. in 99 TERRACE VIEW AVE., BRONX, NY 10463 (NAICS 238220). OSHA activity number 340890631.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MAR-SAL PLUMBING & HEATING, INC.
- Site address
- 99 TERRACE VIEW AVE.
- City
- BRONX
- State
- NY
- ZIP
- 10463
- Mailing
- 84-16 PITKIN AVE., OZONE PARK, NY 11417
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238220
- Employees
- 9
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Feb 12, 2016
- Penalty
- Initial $7,000 · Current $5,250 Reduced
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees; in that employees were exposed to thermal burns due to the ignition of accumulated natural gas: a) On or about 08/20/2015 JFK High School, Bronx, NY. Employee(s) were purging a natural gas pipe-line in the laboratory of a high school, when an employee ignited gas coming from a deck mounted turret valve, causing accumulated gas vapors in the laboratory to ignite, resulting in an explosion. One feasible and acceptable means of abatement, among others, is to follow the NFPA 54/ANSI Z223.1: National Fuel Gas Code. Chapter 8 - Inspection, Testing and Purging, Specifically 8.3.1 Piping Systems Required to Be Purged Outdoors, which states that piping where (1) the design operating gas pressure is greater than 2 psig (14 kPag) or (2) the piping being purged contains one or more sections of pipe or tubing meeting the size and length of table 8.3.1 shall be purged outdoors in accordance with 8.3.1.1 through 8.3.1.4.
Recent events (2)
- · I (S) $5250
- · Z (S) $7000
1926.21 B02
- Issued
- Feb 12, 2016
- Penalty
- Initial $2,800 · Current $2,100 Reduced
1640
General-duty citation text
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his/her environment to control or eliminate any hazards or other exposure to illness or injury: a) On or about 08/20/2015, JFK High School, Bronx, NY. The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to control or eliminate hazards during the process of purging gas-piping.
Recent events (2)
- · I (S) $2100
- · Z (S) $2800
More inspections in this industry (NAICS 238220)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 340890631.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.