Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: KV POWER

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of KV POWER in STAKLEY LEASE SHERIDAN OPERATING, GOLDSMITH, TX 79741 (NAICS 238210). OSHA activity number 340891126.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch KV Power — free Get an email when a new federal OSHA severe-injury report for KV Power is published. One employer, no account, unsubscribe in one click.
Establishment
KV POWER
Site address
STAKLEY LEASE SHERIDAN OPERATING
City
GOLDSMITH
State
TX
ZIP
79741
Mailing
1828 NW AVE. F, ANDREWS, TX 79714
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

5 citations on file for this inspection.

1910.269 C01 I

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 6, 2015
Abate by
Oct 24, 2015
Penalty
Initial $4,900 · Current $4,900
29 CFR 1910.269(c)(1)(i): In assigning an employee or a group of employees to perform a job, the employer did not provide the employees in charge of the job with all available information that relates to the determination of existing characteristics and conditions required by paragraph (a)(4) of this section:  On or about August 23, 2015 at the jobsite the employer did not ensure all pertinent information was provided to employees prior to the start of the task involving electrical repairs and exposed them to electrical shock hazards.
Recent events (3)
  • — F (S) $4900
  • — C (S) $4900
  • — Z (S) $4900

1910.269 D02 I

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Oct 6, 2015
Abate by
Nov 2, 2015
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1910.269(d)(2)(i): The employer shall establish a program consisting of energy control procedures, employee training, and periodic inspections to ensure that, before any employee performs any servicing or maintenance on a machine or equipment where the unexpected energizing, start up, or release of stored energy could occur and cause injury, the machine or equipment is isolated from the energy source and rendered inoperative:  On or about August 23, 2015 at the jobsite the employer did not have established energy control program procedures prior to employees performing electrical work where the unexpected release of stored energy could occur and exposed them to electrical shock hazards.
Recent events (3)
  • — R (S) $0
  • — C (S) $4900
  • — Z (S) $4900

1910.269 L01 III

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 6, 2015
Abate by
Oct 24, 2015
Penalty
Initial $4,900 · Current $4,900
29 CFR 1910.269(l)(1)(iii) Electric lines and equipment was not considered and treated as energized unless they had been de-energized in accordance with paragraph (d) or (m) of this section:    On or about August 23, 2015 at the jobsite the employer did not consider downed electric power lines to be energized and exposed employees to electrical shock hazards.
Recent events (3)
  • — R (S) $4900
  • — C (S) $4900
  • — Z (S) $4900

1910.269 N05

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 6, 2015
Abate by
Oct 24, 2015
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1910.269(n)(5): Testing. The employer shall ensure that, unless a previously installed ground is present, employees test lines and equipment and verify the absence of nominal voltage before employees install any ground on those lines or that equipment:    On or about August 23, 2015 at the jobsite the employer did not test power lines to verify the absence of nominal voltage and exposed employees to electrical shock hazards.
Recent events (3)
  • — R (S) $0
  • — C (S) $4900
  • — Z (S) $4900

1910.269 L03 III

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Oct 6, 2015
Abate by
Oct 24, 2015
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1910.269(l)(3)(iii): The employer did not ensure that any employee approached or take any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless provisions described in (l) (3) (iii) (A) - (C) were followed:   On or about August 23, 2015 at the jobsite the employer did not establish a minimum approach distance to energized power lines and exposed employees to electrical shock hazards.
Recent events (3)
  • — R (S) $0
  • — C (S) $4900
  • — Z (S) $4900

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340891126.